|
EWAT085B-SRA1 |
EWAT115B-SRA1 |
EWAT135B-SRA1 |
EWAT155B-SRA2 |
EWAT175B-SRA1 |
EWAT195B-SRA2 |
EWAT205B-SRA2 |
EWAT215B-SRA1 |
EWAT240B-SRA2 |
EWAT260B-SRA2 |
EWAT290B-SRA1 |
EWAT310B-SRA2 |
EWAT330B-SRA2 |
EWAT340B-SRA1 |
EWAT350B-SRA2 |
EWAT420B-SRA2 |
EWAT460B-SRA2 |
EWAT510B-SRA2 |
EWAT570B-SRA2 |
EWAT610B-SRA2 |
EWAT670B-SRA2 |
Cooling capacity |
Nom. |
kW |
76.32 |
104.78 |
123.67 |
149.61 |
164.58 |
180.89 |
199.92 |
203.05 |
230.33 |
247.63 |
265.52 |
289.52 |
310.75 |
328.17 |
329.79 |
397.33 |
441.96 |
486.05 |
532.44 |
576.51 |
634.99 |
|
Rated |
kW |
76.32 |
104.78 |
123.67 |
149.61 |
164.58 |
180.89 |
199.92 |
203.05 |
230.33 |
247.63 |
265.52 |
289.52 |
310.75 |
328.17 |
329.79 |
397.33 |
441.96 |
486.05 |
532.44 |
576.51 |
634.99 |
Capacity control |
Method |
|
Staged |
Staged |
Staged |
Variable |
Staged |
Variable |
Variable |
Staged |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
|
Minimum capacity |
% |
50 |
38 |
50 |
25 |
38 |
21 |
19 |
50 |
17 |
25 |
24 |
14 |
13 |
33 |
19 |
17 |
15 |
14 |
12 |
11 |
17 |
Power input |
Cooling |
Nom. |
kW |
33.8 |
40.3 |
53.1 |
65.9 |
72.8 |
73.2 |
84.7 |
91.9 |
89.1 |
100 |
115 |
118 |
129 |
122 |
140 |
147 |
181 |
197 |
230 |
244 |
251 |
EER |
2.26 |
2.6 |
2.33 |
2.27 |
2.26 |
2.47 |
2.36 |
2.21 |
2.59 |
2.48 |
2.3 |
2.44 |
2.41 |
2.69 |
2.35 |
2.7 |
2.43 |
2.46 |
2.31 |
2.35 |
2.53 |
ESEER |
3.95 |
4.07 |
3.9 |
3.81 |
4.1 |
3.88 |
3.97 |
3.73 |
4.09 |
3.89 |
4.12 |
4.05 |
3.96 |
4.2 |
3.97 |
4.09 |
4.13 |
4.02 |
4.13 |
4.01 |
4.1 |
IPLV |
4.67 |
4.97 |
4.5 |
4.63 |
4.74 |
4.62 |
4.72 |
4.36 |
4.88 |
4.63 |
4.84 |
4.83 |
4.72 |
5.01 |
4.7 |
4.81 |
4.86 |
4.75 |
4.84 |
4.84 |
4.89 |
SEER |
3.8 |
4.11 |
3.8 |
3.8 |
4.17 |
3.9 |
3.92 |
3.82 |
4.29 |
4.01 |
4.26 |
4.2 |
4.26 |
4.4 |
4.04 |
4.42 |
4.35 |
4.41 |
4.3 |
4.37 |
4.41 |
Dimensions |
Unit |
Depth |
mm |
2,120 |
2,660 |
2,660 |
3,570 |
3,180 |
4,170 |
4,170 |
3,780 |
2,326 |
2,326 |
2,326 |
3,226 |
3,226 |
3,226 |
3,226 |
4,126 |
4,126 |
4,126 |
4,126 |
5,025 |
5,874 |
|
|
Height |
mm |
1,801 |
1,801 |
1,801 |
1,822 |
1,801 |
1,822 |
1,822 |
1,822 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
2,540 |
|
|
Width |
mm |
1,204 |
1,204 |
1,204 |
1,204 |
1,204 |
1,204 |
1,204 |
1,204 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
2,236 |
Weight |
Operation weight |
kg |
696 |
783 |
830 |
1,035 |
1,006 |
1,198 |
1,190 |
1,210 |
1,822 |
1,849 |
1,951 |
2,268 |
2,296 |
2,350 |
2,324 |
2,784 |
2,954 |
3,111 |
3,360 |
3,762 |
4,089 |
|
Unit |
kg |
689 |
773 |
820 |
1,026 |
993 |
1,185 |
1,177 |
1,191 |
1,815 |
1,843 |
1,935 |
2,251 |
2,277 |
2,330 |
2,304 |
2,754 |
2,921 |
3,078 |
3,312 |
3,718 |
4,053 |
Casing |
Colour |
|
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
Ivory white |
|
Material |
|
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Galvanized and painted steel sheet |
Water heat exchanger |
Type |
|
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
Brazed plate |
|
Water flow rate |
Cooling |
Nom. |
l/s |
3.7 |
5 |
5.9 |
7.2 |
7.9 |
8.7 |
9.6 |
9.7 |
11 |
11.9 |
12.7 |
13.9 |
14.9 |
15.7 |
15.8 |
19 |
21.2 |
23.3 |
25.5 |
27.6 |
30.4 |
|
Water pressure drop |
Cooling |
Nom. |
kPa |
24.6 |
32.2 |
23.8 |
58.5 |
37.5 |
41.6 |
49.9 |
36.8 |
64.5 |
73.5 |
59.9 |
42.1 |
47.8 |
71.7 |
53.2 |
50.4 |
61.1 |
72.7 |
58.9 |
68 |
81 |
|
Water volume |
l |
5 |
6 |
9 |
7 |
12 |
11 |
11 |
16 |
11 |
11 |
16 |
19 |
19 |
20 |
19 |
28 |
28 |
28 |
42 |
42 |
42 |
|
Insulation material |
|
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Closed cell |
Air heat exchanger |
Type |
|
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Heat exchanger |
Indoor side |
|
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
water |
|
Outdoor side |
|
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Air |
Fan |
Quantity |
|
4 |
6 |
6 |
8 |
8 |
10 |
10 |
10 |
4 |
4 |
4 |
5 |
5 |
6 |
5 |
7 |
7 |
8 |
8 |
9 |
11 |
|
Type |
|
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
Direct propeller |
|
Air flow rate |
Nom. |
l/s |
4,929 |
7,396 |
7,396 |
11,352 |
9,838 |
14,202 |
14,202 |
12,325 |
17,064 |
17,064 |
17,064 |
21,330 |
21,330 |
25,596 |
21,330 |
29,862 |
29,862 |
34,128 |
34,128 |
38,394 |
46,926 |
|
|
Cooling |
Rated |
m³/h |
17,744.4 |
26,625.6 |
26,625.6 |
40,867.2 |
35,416.8 |
51,127.2 |
51,127.2 |
44,370 |
61,430.4 |
61,430.4 |
61,430.4 |
76,788 |
76,788 |
92,145.6 |
76,788 |
107,503.2 |
107,503.2 |
122,860.8 |
122,860.8 |
138,218.4 |
168,933.6 |
|
Diameter |
mm |
450 |
450 |
450 |
450 |
450 |
450 |
450 |
450 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
|
Speed |
rpm |
1,200 |
1,200 |
1,200 |
1,200 |
1,200 |
1,200 |
1,200 |
1,200 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
780 |
Fan motor |
Drive |
|
Phase cut |
Phase cut |
Phase cut |
Phase cut |
Phase cut |
Phase cut |
Phase cut |
Phase cut |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
VFD driven |
|
Input |
Cooling |
W |
1,400 |
2,200 |
2,200 |
2,900 |
2,900 |
3,600 |
3,600 |
3,600 |
4,700 |
4,700 |
4,700 |
5,900 |
5,900 |
7,100 |
5,900 |
8,200 |
8,200 |
9,400 |
9,400 |
10,600 |
12,900 |
Compressor |
Quantity |
|
2 |
2 |
2 |
4 |
2 |
4 |
4 |
2 |
4 |
4 |
3 |
4 |
4 |
3 |
4 |
4 |
5 |
5 |
6 |
6 |
6 |
|
Type |
|
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
|
Driver |
|
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
Electric motor |
|
Oil |
Charged volume |
l |
6.5 |
7.69 |
8.88 |
13 |
10.7 |
14.1 |
15.3 |
12.6 |
16.5 |
17.7 |
17 |
19.1 |
20.2 |
18.9 |
21.4 |
23.3 |
27.7 |
29.6 |
34 |
35.9 |
37.8 |
Operation range |
Air side |
Cooling |
Max. |
°CDB |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
|
|
|
Min. |
°CDB |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
-18 |
|
Water side |
Cooling |
Max. |
°CDB |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
|
|
|
Min. |
°CDB |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
-13 |
Sound power level |
Cooling |
Nom. |
dBA |
78.6 |
82.5 |
84.1 |
81.6 |
86.3 |
83.9 |
85.2 |
87.8 |
87 |
87.2 |
87.5 |
88.2 |
88.3 |
89.1 |
88.4 |
89.8 |
89.8 |
90.4 |
90.5 |
91 |
91.8 |
Sound pressure level |
Cooling |
Nom. |
dBA |
61.2 |
64.7 |
66.4 |
63.3 |
68.3 |
65.3 |
66.6 |
69.4 |
68.1 |
68.2 |
68.5 |
68.7 |
68.8 |
69.6 |
68.9 |
69.8 |
69.9 |
70.5 |
70.5 |
70.6 |
71.1 |
Refrigerant |
Type |
|
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
R-32 |
|
GWP |
|
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
675 |
|
Circuits |
Quantity |
|
1 |
1 |
1 |
2 |
1 |
2 |
2 |
1 |
2 |
2 |
1 |
2 |
2 |
1 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
|
Charge |
kg |
10 |
11 |
12.5 |
15 |
14 |
18 |
18 |
17 |
36 |
38 |
36 |
42 |
43 |
50 |
44 |
57 |
58 |
60 |
62 |
80 |
90 |
Charge |
Per circuit |
kgCO2Eq |
6,750 |
7,425 |
8,437.5 |
5,062.5 |
9,450 |
6,075 |
6,075 |
11,475 |
12,150 |
12,825 |
24,300 |
14,175 |
14,512.5 |
33,750 |
14,850 |
19,237.5 |
19,575 |
20,250 |
20,925 |
27,000 |
30,375 |
Piping connections |
Evaporator water inlet/outlet (OD) |
|
76.1 |
76.1 |
76.1 |
88.9 |
76.1 |
88.9 |
88.9 |
76.1 |
88.9 |
88.9 |
76.1 |
88.9 |
88.9 |
76.1 |
88.9 |
88.9 |
88.9 |
88.9 |
114.3 |
114.3 |
114.3 |
Space cooling |
A Condition 35°C |
Pdc |
kW |
76.32 |
104.78 |
123.67 |
149.61 |
164.58 |
180.89 |
199.92 |
203.05 |
230.33 |
247.63 |
265.52 |
289.52 |
310.75 |
328.17 |
329.79 |
397.33 |
441.96 |
486.05 |
532.44 |
576.51 |
634.99 |
|
|
EERd |
|
2.26 |
2.6 |
2.33 |
2.27 |
2.26 |
2.47 |
2.36 |
2.21 |
2.59 |
2.48 |
2.3 |
2.44 |
2.41 |
2.69 |
2.35 |
2.7 |
2.43 |
2.46 |
2.31 |
2.35 |
2.53 |
|
B Condition 30°C |
Pdc |
kW |
51.19 |
80.57 |
91.52 |
100.44 |
131.13 |
129.67 |
156.34 |
135.52 |
160.86 |
183.25 |
208.66 |
233.2 |
216.78 |
266.18 |
244.04 |
275.1 |
343.81 |
347.76 |
417.51 |
398.85 |
469.89 |
|
|
EERd |
|
3.95 |
3.86 |
3.55 |
3.91 |
3.58 |
3.77 |
3.61 |
3.84 |
3.92 |
3.52 |
3.56 |
3.73 |
3.88 |
3.78 |
3.38 |
3.96 |
3.64 |
3.76 |
3.56 |
3.69 |
3.77 |
|
C Condition 25°C |
Pdc |
kW |
35.87 |
49.25 |
58.13 |
70.32 |
77.35 |
85.02 |
93.96 |
95.43 |
108.25 |
116.39 |
124.8 |
136.07 |
146.05 |
155.88 |
155 |
186.75 |
187.7 |
245.52 |
246.57 |
247.85 |
308.38 |
|
|
EERd |
|
4.66 |
4.96 |
4.56 |
4.57 |
4.89 |
4.69 |
4.76 |
4.31 |
4.95 |
4.78 |
5.03 |
4.71 |
4.7 |
5.24 |
4.76 |
4.9 |
5.11 |
4.99 |
5.02 |
5.12 |
5.18 |
|
D Condition 20°C |
Pdc |
kW |
16.03 |
22 |
25.97 |
31.42 |
34.56 |
37.99 |
41.98 |
42.64 |
48.37 |
52 |
55.76 |
63.04 |
63 |
68.92 |
69.26 |
83.44 |
100.28 |
100.28 |
111.81 |
121.07 |
133.35 |
|
|
EERd |
|
5.06 |
5.52 |
4.82 |
5.29 |
5.53 |
5.27 |
5.45 |
4.54 |
6.45 |
5.66 |
6.44 |
6.51 |
6.49 |
5.65 |
5.86 |
6.23 |
6.46 |
6.72 |
6.71 |
6.48 |
6.08 |
|
ηs,c |
% |
149 |
161.4 |
149 |
149 |
163.8 |
153 |
153.8 |
149.8 |
168.6 |
157.4 |
167.4 |
165 |
167.4 |
173 |
158.6 |
173.8 |
171 |
173.4 |
169 |
171.8 |
173.4 |
General |
Supplier/Manufacturer details |
Name and address |
|
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy |
LW(A) Sound power level (according to EN14825) |
dB(A) |
61.2 |
64.7 |
66.4 |
63.3 |
68.3 |
65.3 |
66.6 |
69.4 |
68.1 |
68.2 |
68.5 |
68.7 |
68.8 |
69.6 |
68.9 |
69.8 |
69.9 |
70.5 |
70.5 |
70.6 |
71.1 |
Cooling |
Cdc (Degradation cooling) |
|
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
Standard rating conditions used |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Medium temperature application |
Power consumption in other than active mode |
Crankcase heater mode |
PCK |
W |
0.066 |
0.066 |
0.066 |
0.132 |
0.066 |
0.132 |
0.132 |
0.066 |
0.132 |
0.132 |
0.099 |
0.132 |
0.132 |
0.099 |
0.132 |
0.132 |
0.165 |
0.165 |
0.198 |
0.198 |
0.198 |
|
Off mode |
POFF |
W |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
Standby mode |
Cooling |
PSB |
W |
0.1 |
0.1 |
0.1 |
0.2 |
0.1 |
0.2 |
0.2 |
0.1 |
0.2 |
0.2 |
0.15 |
0.2 |
0.2 |
0.15 |
0.2 |
0.2 |
0.25 |
0.25 |
0.3 |
0.3 |
0.3 |
|
Thermostat-off mode |
PTO |
Cooling |
W |
0.156 |
0.166 |
0.196 |
0.232 |
0.196 |
0.262 |
0.262 |
0.216 |
0.262 |
0.262 |
0.249 |
0.312 |
0.312 |
0.259 |
0.312 |
0.342 |
0.375 |
0.375 |
0.438 |
0.438 |
0.438 |
Power supply |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
|
Voltage range |
Min. |
% |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
|
Max. |
% |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Unit |
Starting current |
Max |
A |
213 |
313 |
324 |
284 |
462 |
384 |
395 |
498 |
411 |
422 |
546 |
572 |
583 |
587 |
595 |
635 |
680 |
717 |
761 |
798 |
839 |
|
Running current |
Cooling |
Nom. |
A |
62 |
71 |
87 |
119 |
119 |
128 |
143 |
151 |
151 |
165 |
189 |
203 |
216 |
202 |
231 |
245 |
298 |
324 |
378 |
402 |
414 |
|
|
Max |
A |
73 |
86 |
96 |
143 |
132 |
156 |
167 |
168 |
183 |
195 |
215 |
241 |
253 |
256 |
264 |
305 |
349 |
386 |
431 |
467 |
508 |
|
Max unit current for wires sizing |
A |
80 |
94 |
106 |
157 |
146 |
171 |
183 |
185 |
202 |
214 |
237 |
265 |
278 |
282 |
290 |
335 |
384 |
425 |
474 |
514 |
559 |
Fans |
Nominal running current (RLA) |
A |
3 |
5 |
5 |
6 |
6 |
8 |
8 |
8 |
9 |
9 |
9 |
11 |
11 |
13 |
11 |
15 |
15 |
17 |
17 |
19 |
24 |
Compressor |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
|
Voltage range |
Min. |
% |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
|
Max. |
% |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
|
Maximum running current |
A |
66 |
91 |
88 |
131 |
152 |
185 |
182 |
157 |
180 |
177 |
230 |
222 |
248 |
235 |
245 |
309 |
383 |
387 |
461 |
466 |
470 |
|
Starting method |
|
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Notes |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
|
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
(2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 |
|
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
(3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated form sound power level and used for info only, not considered bounding |
|
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
|
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
|
(6) - All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
(6) - All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
All data refers to the standard unit without options. |
|
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
(7) - All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
All data are subject to change without notice. Please refer to the unit nameplate data. |
|
(8) - The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
(8) - The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
The value refers to the pressure drop in the evaporator only |
|
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
(9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans |
|
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
|
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
(11) - In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
In case of inverter driven units, no inrush current at start up is experienced. |
|
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
|
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
|
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
(14) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
Maximum unit current for wires sizing is based on minimum allowed voltage. |
|
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
|
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |