EWWH370VZPSA1 EWWH530VZPSA1 EWWH680VZPSA1 EWWH880VZPSA2 EWWHC12VZPSA2 EWWHC13VZPSA2
Cooling capacity Nom. kW 369 525 677 884 1,180 1,295
  Rated kW 369.3 525.1 677.11 883.79 1,180.43 1,295.36
Capacity control Method   Variable Variable Variable Variable Variable Variable
  Minimum capacity % 20 20 20 10 10 10
Power input Cooling Nom. kW 64.7 94.9 119 166 221 247
EER 5.71 5.53 5.67 5.34 5.35 5.25
ESEER 7.9 8.64 8.83 8.54 8.85 9
IPLV 9.13 9.68 9.96 9.37 9.56 9.61
SEER 8.12 9.02 9.29 8.56 9.01 8.92
Dimensions Unit Depth mm 3,750 3,822 3,822 4,508 4,750 4,874
    Height mm 2,108 2,430 2,487 2,302 2,500 2,493
    Width mm 1,179 1,287 1,303 1,579 1,610 1,769
Weight Unit kg 3,247 4,082 4,346 6,310 7,530 8,250
  Operation weight kg 3,375 4,349 4,660 6,900 8,300 9,200
Casing Colour   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
  Material   Painted galvanized steel plate Painted galvanized steel plate Painted galvanized steel plate Painted galvanized steel plate Painted galvanized steel plate Painted galvanized steel plate
Water heat exchanger Water flow rate Cooling Nom. l/s 17.7 25.1 32.3 42.2 56.4 61.9
  Water pressure drop Cooling Nom. kPa 32 25 27 20 26 23
Water heat exchanger - evaporator Type   Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube
  Fluid   Water Water Water Water Water Water
  Fouling factor   0 0 0 0 0 0
  Water volume l 96 168 199 320 380 480
  Water temperature in Cooling °C 12 12 12 12 12 12
  Water temperature out Cooling °C 7 7 7 7 7 7
  Water flow rate Cooling Nom. l/s 17.7 25.1 32.3 42.2 56.4 61.9
  Water pressure drop Cooling Nom. kPa 32 25 27 20 26 23
  Insulation material   Closed cell Closed cell Closed cell Closed cell Closed cell Closed cell
Water heat exchanger - condenser Type   Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube
  Fluid   Water Water Water Water Water Water
  Fouling factor   0 0 0 0 0 0
  Water volume l 126 217 241 270 390 470
  Water temperature in Cooling °C 30 30 30 30 30 30
  Water temperature out Cooling °C 35 35 35 35 35 35
  Water flow rate Cooling Nom. l/s 21.1 30.1 38.9 50.9 68 74.9
  Water pressure drop Cooling Nom. kPa 9 9 12 13 12 16
Heat exchanger Indoor side   water water water water water water
  Outdoor side   water water water water water water
Compressor Type   Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression
  Driver   Electric motor Electric motor Electric motor Electric motor Electric motor Electric motor
  Oil Charged volume l 36 40 50 68 86 86
  Quantity   1 1 1 2 2 2
Sound power level Cooling Nom. dBA 99 105 105 106 107 109
Sound pressure level Cooling Nom. dBA 80 86 86 87 88 89
Refrigerant Charge kg 100 150 180 290 320 350
  Circuits Quantity   1 1 1 2 2 2
  GWP   7 7 7 7 7 7
Charge Per circuit kgCO2Eq 700 1,050 1,260 1,015 1,120 1,225
Refrigerant circuit Charge kg 100 150 180 290 320 350
Piping connections Evaporator water inlet/outlet mm 139.7 219.1 219.1 219.1 219.1 273
  Condenser water inlet/outlet (OD)   219.1mm 219.1mm 219.1mm 219.1 / 219.1 mm 219.1 / 219.1 mm 219.1 / 219.1 mm
General Supplier/Manufacturer details Name and address   Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy Daikin Applied Europe - Via Piani di S.Maria 72, 00040 Ariccia (Roma), Italy
LW(A) Sound power level (according to EN14825) dB(A) 99 105 105 106 107 109
Space cooling A Condition (35°C - 27/19) EERd   5.71 5.53 5.67 5.34 5.35 5.25
    Pdc kW 369.3 525.1 677.11 883.79 1,180.43 1,295.36
  B Condition (30°C - 27/19) EERd   7.22 7.59 7.52 7.22 7.37 7.31
    Pdc kW 273.48 388.8 501.4 654.34 874.17 959.23
  C Condition (25°C - 27/19) EERd   9.56 10.08 10.71 9.6 10.28 10.3
    Pdc kW 173.84 247.07 318.65 415.8 555.51 609.53
  D Condition (20°C - 27/19) EERd   8.22 11.2 11.44 10.43 11.28 10.93
    Pdc kW 77.58 110.25 142.21 185.63 248.07 272.16
  ηs,c % 316.8 352.8 363.6 334.4 352.4 348.8
Cooling Cdc (Degradation cooling)   0.9 0.9 0.9 0.9 0.9 0.9
Standard rating conditions used Medium temperature application Medium temperature application Medium temperature application Medium temperature application Medium temperature application Medium temperature application
Power consumption in other than active mode Crankcase heater mode PCK W 0 0 0 0 0 0
  Off mode POFF W 0 0 0 0 0 0
  Standby mode Cooling PSB W 0.05 0.05 0.05 0.1 0.1 0.1
  Thermostat-off mode PTO Cooling W 0.18 0.23 0.27 0.19 0.23 0.26
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400
  Voltage range Min. % -10 -10 -10 -10 -10 -10
    Max. % 10 10 10 10 10 10
Unit Running current Cooling Nom. A 104.0 150.0 185.0 257.0 338.0 378.0
    Max A 199.0 246.0 277.0 445.0 523.0 649.0
Compressor Phase   3~ 3~ 3~ 3~ 3~ 3~
  Voltage V 40 40 40 40 40 40
  Voltage range Min. % -10 -10 -10 -10 -10 -10
    Max. % 10 10 10 10 10 10
  Starting method   VFD driven VFD driven VFD driven VFD driven VFD driven VFD driven
Notes All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
  Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
  Maximum running current is based on max compressor absorbed current in its envelope Maximum running current is based on max compressor absorbed current in its envelope Maximum running current is based on max compressor absorbed current in its envelope Maximum running current is based on max compressor absorbed current in its envelope Maximum running current is based on max compressor absorbed current in its envelope Maximum running current is based on max compressor absorbed current in its envelope
  Maximum unit current for wires sizing is based on minimum allowed voltage. Maximum unit current for wires sizing is based on minimum allowed voltage. Maximum unit current for wires sizing is based on minimum allowed voltage. Maximum unit current for wires sizing is based on minimum allowed voltage. Maximum unit current for wires sizing is based on minimum allowed voltage. Maximum unit current for wires sizing is based on minimum allowed voltage.
  Maximum current for wires sizing: compressor full load ampere x 1.1 Maximum current for wires sizing: compressor full load ampere x 1.1 Maximum current for wires sizing: compressor full load ampere x 1.1 Maximum current for wires sizing: compressor full load ampere x 1.1 Maximum current for wires sizing: compressor full load ampere x 1.1 Maximum current for wires sizing: compressor full load ampere x 1.1
  All data refers to the standard unit without options. All data refers to the standard unit without options. All data refers to the standard unit without options. All data refers to the standard unit without options. All data refers to the standard unit without options. All data refers to the standard unit without options.
  All data are subject to change without notice. Please refer to the unit nameplate data. All data are subject to change without notice. Please refer to the unit nameplate data. All data are subject to change without notice. Please refer to the unit nameplate data. All data are subject to change without notice. Please refer to the unit nameplate data. All data are subject to change without notice. Please refer to the unit nameplate data. All data are subject to change without notice. Please refer to the unit nameplate data.
  For more details on the operating limits please refer to the Chiller Selection Software (CSS). For more details on the operating limits please refer to the Chiller Selection Software (CSS). For more details on the operating limits please refer to the Chiller Selection Software (CSS). For more details on the operating limits please refer to the Chiller Selection Software (CSS). For more details on the operating limits please refer to the Chiller Selection Software (CSS). For more details on the operating limits please refer to the Chiller Selection Software (CSS).
  Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
  In case of inverter driven units, no inrush current at start up is experienced. In case of inverter driven units, no inrush current at start up is experienced. In case of inverter driven units, no inrush current at start up is experienced. In case of inverter driven units, no inrush current at start up is experienced. In case of inverter driven units, no inrush current at start up is experienced. In case of inverter driven units, no inrush current at start up is experienced.