FAA100AUVEB / RZQG71L9V1B FAA71AUVEB / RZQG71L9V1B FAA100AUVEB / RZQG100L9V1B
Indoor unit   FAA71AUVEB FAA100AUVEB
Outdoor unit   RZQG71L9V1 RZQG100L9V1
Cooling capacity Nom. kW   6.80 (1) 9.50 (1)
Heating capacity Nom. kW   7.50 (2) 10.8 (2)
Power input Cooling Nom. kW   2.00 (3) 2.63 (3)
  Heating Nom. kW   2.03 (3) 3.00 (3)
Nominal efficiency EER   3.40 (3) 3.62 (3)
  COP   3.70 (3) 3.61 (3)
  Annual energy consumption kWh   1,000 (0.000) 1,315 (0.000)
  Energy labeling Directive Cooling   A A
    Heating   A A
Space cooling Energy efficiency class   A++ A++ A++
  Capacity Pdesign kW 6.80 6.80 9.50
  SEER   6.43 6.43 6.11
  Annual energy consumption kWh/a 371 371 545
  A Condition (35°C - 27/19) Pdc kW 6.80 6.80 9.50
    EERd   3.40 3.40 3.62
    Power input kW 2.00 2.00 2.63
  B Condition (30°C - 27/19) Pdc kW 5.08 5.08 7.00
    EERd   4.33 4.33 4.20
    Power input kW 1.18 1.18 1.67
  C Condition (25°C - 27/19) Pdc kW 3.86 3.86 5.40
    EERd   9.26 9.26 8.31
    Power input kW 0.420 0.42 0.65
  D Condition (20°C - 27/19) Pdc kW 3.97 3.97 5.53
    EERd   12.2 12.19 10.56
    Power input kW 0.330 0.33 0.53
Space heating (Average climate) Energy efficiency class   A+ A+ A+
  Capacity Pdesign kW 6.33 6.33 10.2
  SCOP/A   4.02 4.02 4.01
  SCOPnet/A   4.03 4.03 4.03
  Pdh Heating capacity at -10° kW 5.93 6 9
  Annual energy consumption kWh/a 2,205 2,205 3,562
  Required back up heating cap at design conditions kW 0.40 0.400 1.40
  TOL Tol (temperature operating limit) °C -15 -15 -15
    Pdh (declared heating cap) kW 6.48 6.48 8.43
    COPd (declared COP)   1.98 1.98 2.24
    Power input kW 3.28 3.28 3.77
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7
    Pdh (declared heating cap) kW 5.60 5.60 9.02
    COPd (declared COP)   2.77 2.77 3.19
    Power input kW 2.03 2.03 2.83
  A Condition (-7°C) Pdh (declared heating cap) kW 5.60 5.60 9.02
    COPd (declared COP)   2.77 2.77 3.19
    Power input kW 2.03 2.03 2.83
  B Condition (2°C) Pdh (declared heating cap) kW 4.52 4.52 5.96
    COPd (declared COP)   3.77 3.77 3.41
    Power input kW 1.20 1.20 1.75
  C Condition (7°C) Pdh (declared heating cap) kW 2.88 2.88 4.02
    COPd (declared COP)   6.45 6.45 6.07
    Power input kW 0.450 0.45 0.67
  D Condition (12°C) Pdh (declared heating cap) kW 3.27 3.27 4.58
    COPd (declared COP)   7.41 7.41 6.94
    Power input kW 0.45 0.45 0.66
Power consumption in other than active mode Off mode Cooling POFF kW   0.000 0.000
    Heating POFF kW   0.000 0.000
  Standby mode Cooling PSB kW   0.009 0.009
    Heating PSB kW   0.009 0.009
  Thermostat-off mode Cooling PTO kW   0.007 0.009
    Heating PTO kW   0.007 0.009
  Standby mode Cooling PSB W 9.10    
    Heating PSB W 9.1    
  Crankcase heater mode PCK W 0.00    
    POFF W 0.00    
Pto (Thermostat off) W 7.000    
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25
Cooling function included Yes Yes Yes
Heating function included Yes Yes Yes
Average climate included Yes Yes Yes
Cold season included No No No
Warm season included No No No
Ecolabel logo No No No
Eurovent Sound power level outdoor Cooling Nom. dBA 64 64 66
  Sound power level indoor Cooling Nom. dBA 65 61 65
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW   0.000 0.000
    Heating PCK kW   0.000 0.000
Notes   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
    Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
    EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only