FBA100A2VEB / RZQG71L8Y1B FBA140A2VEB / RZQG140L7Y1B FBA71A2VEB / RZQG71L8Y1B FBA140A2VEB / RZQG100L8Y1B FBA100A2VEB / RZQG100L8Y1B FBA140A2VEB / RZQG125L8Y1B FBA125A2VEB / RZQG125L8Y1B
Indoor unit   FBA140A2VEB FBA71A2VEB   FBA100A2VEB   FBA125A2VEB
Outdoor unit RZQG71L8Y1 RZQG140LY1 RZQG71L8Y1 RZQG100L8Y1 RZQG100L8Y1 RZQG125L8Y1 RZQG125L8Y1
Cooling capacity Nom. kW   13.4 (1) 6.80 (1)   9.50 (1)   12.0 (1)
Heating capacity Nom. kW   15.5 (2) 7.50 (2)   10.8 (2)   13.5 (2)
Power input Cooling Nom. kW   5.00 (3) 1.89 (3)   2.49 (3)   3.63 (3)
  Heating Nom. kW   4.31 (3) 1.87 (3)   2.45 (3)   3.46 (3)
Nominal efficiency EER   2.68 (3) 3.60 (3)   3.81 (3)   3.31 (3)
  COP   3.60 (3) 4.01 (3)   4.41 (3)   3.90 (3)
  Annual energy consumption kWh     944   1,247 (0.000)   1,813 (0.000)
  Energy labeling Directive Cooling     A   A   A
    Heating     A   A   A
Space cooling Energy efficiency class   A++   A++ A+ A+ A++ A++
  Capacity Pdesign kW 6.80 13.4 6.80 9.50 9.50 12.0 12.0
  SEER   6.16 6.14 6.16 5.87 5.87 6.11 6.11
  ηs,c %   242.7          
  Annual energy consumption kWh/a 386 1,309 386 567 566 688 687
  A Condition (35°C - 27/19) Pdc kW 6.80 13.40 6.80 9.50 9.50 12.0 12.00
    EERd   3.60 2.68 3.60 3.81 3.81 3.31 3.31
    Power input kW 1.89 5.00 1.89 2.50 2.49 3.63 3.63
  B Condition (30°C - 27/19) Pdc kW 5.01 9.88 5.01 7.00 7.00 8.84 8.84
    EERd   5.44 4.73 5.44 4.41 4.41 5.11 5.11
    Power input kW 0.92 2.09 0.92 1.59 1.59 1.73 1.73
  C Condition (25°C - 27/19) Pdc kW 3.95 6.35 3.95 5.46 5.46 5.68 5.68
    EERd   8.13 7.71 8.13 8.13 8.13 7.89 7.89
    Power input kW 0.49 0.82 0.49 0.67 0.67 0.72 0.72
  D Condition (20°C - 27/19) Pdc kW 4.08 5.95 4.08 5.80 5.80 5.61 5.61
    EERd   10.20 10.07 10.20 10.51 10.51 9.88 9.88
    Power input kW 0.40 0.59 0.40 0.56 0.55 0.57 0.57
Space heating (Average climate) Energy efficiency class   A+   A+ A++ A++ A+ A+
  Capacity Pdesign kW 6.00 11.6 6.00 11.3 11.3 12.7 12.7
  SCOP/A   4.31 4.01 4.31 4.78 4.78 4.28 4.28
  SCOPnet/A   4.35 4.01 4.35 4.85 4.85 4.32 4.32
  ηs,h %   157.3          
  Pdh Heating capacity at -10° kW     5   8   10
  Annual energy consumption kWh/a 1,949 4,043 1,949 3,310 3,310 4,155 4,154
  Required back up heating cap at design conditions kW 1.09 0.00 1.10 3.19 3.20 3.22 3.06
  TOL Tol (temperature operating limit) °C -15 -10 -15 -15 -15 -15 -15
    Pdh (declared heating cap) kW 4.22 11.57 4.22 4.94 4.94 6.56 6.56
    COPd (declared COP)   2.07 2.27 2.07 2.70 2.70 2.02 2.02
    Power input kW 2.04 5.11 2.04 1.83 1.83 3.25 3.25
  TBivalent Tbiv (bivalent temperature) °C -7 -10 -7 -7 -7 -7 -7
    Pdh (declared heating cap) kW 5.31 11.57 5.31 10.0 10.00 11.2 11.23
    COPd (declared COP)   3.00 2.27 3.00 3.54 3.54 2.71 2.71
    Power input kW 1.77 5.11 1.77 2.83 2.82 4.14 4.14
  A Condition (-7°C) Pdh (declared heating cap) kW 5.31 10.24 5.31 10.0 10.00 11.2 11.23
    COPd (declared COP)   3.00 2.68 3.00 3.54 3.54 2.71 2.71
    Power input kW 1.77 3.83 1.77 2.83 2.82 4.14 4.14
  B Condition (2°C) Pdh (declared heating cap) kW 3.23 6.23 3.23 6.08 6.08 6.84 6.84
    COPd (declared COP)   4.48 3.97 4.48 4.77 4.77 4.36 4.36
    Power input kW 0.730 1.57 0.72 1.28 1.27 1.57 1.57
  C Condition (7°C) Pdh (declared heating cap) kW 2.87 4.11 2.87 3.91 3.91 4.47 4.47
    COPd (declared COP)   5.35 5.10 5.35 5.71 5.71 5.38 5.38
    Power input kW 0.536 0.81 0.54 0.685 0.68 0.831 0.83
  D Condition (12°C) Pdh (declared heating cap) kW 3.32 4.79 3.32 4.00 4.00 4.64 4.64
    COPd (declared COP)   6.40 6.03 6.40 7.18 7.18 6.76 6.76
    Power input kW 0.52 0.79 0.52 0.56 0.56 0.69 0.69
Pto (Thermostat off) W 3.0     4.0   4.0  
Power consumption in other than active mode Standby mode Cooling PSB W 14.5     22.0   22.0  
  Crankcase heater mode PCK W 0.00     0.00   0.00  
  Off mode POFF W 14.5     22.0   22.0  
Indication if the heater is equipped with a supplementary heater (pair application)   No          
Supplementary heater (pair application) Back-up capacity Heating elbu kW   0.0          
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25 0.25 0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25 0.25 0.25 0.25 0.25
Cooling function included Yes Yes Yes Yes Yes Yes Yes
Heating function included Yes Yes Yes Yes Yes Yes Yes
Average climate included Yes Yes Yes Yes Yes Yes Yes
Cold season included No No No No No No No
Warm season included No No No No No No No
Ecolabel logo No No No No No No No
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW   0.000 0.000   0.000   0.000
    Heating PCK kW   0.014 0.000   0.000   0.000
  Off mode Cooling POFF kW   0.014 0.015   0.022   0.022
    Heating POFF kW   0.014 0.015   0.022   0.022
  Standby mode Cooling PSB kW   0.014 0.015   0.022   0.022
    Heating PSB kW   0.014 0.015   0.022   0.022
  Thermostat-off mode Cooling PTO kW   0.000 0.003   0.004   0.004
    Heating PTO kW   0.014 0.003   0.004   0.004
Notes   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
    Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m   Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m   Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
    EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only