FCAG71AVEB / AZAS71M2V1B |
FCAG100AVEB / AZAS100M7V1B |
FCAG125AVEB / AZAS125M7V1B |
FCAG140AVEB / AZAS140M7V1B |
Indoor unit |
FCAG71AVEB |
FCAG100AVEB |
FCAG125AVEB |
FCAG140AVEB |
Outdoor unit |
AZAS71M2V1B |
AZAS100M7V1B |
AZAS125M7V1B |
AZAS140M7V1B |
Cooling capacity |
Nom. |
kW |
6.80 (1) |
9.50 (1) |
12.1 (1) |
13.4 (1) |
Heating capacity |
Nom. |
kW |
7.50 (2) |
10.8 (2) |
13.5 (2) |
15.5 (2) |
Space cooling |
Energy efficiency class |
|
A+ |
A+ |
|
|
|
Capacity |
Pdesign |
kW |
6.80 |
9.50 |
12.1 |
13.0 |
|
SEER |
|
5.87 |
5.67 |
5.40 |
6.00 |
|
ηs,c |
% |
|
|
213 |
237 |
|
Annual energy consumption |
kWh/a |
405 |
586 |
1,345 |
1,300 |
|
A Condition (35°C - 27/19) |
Pdc |
kW |
6.80 |
9.50 |
12.10 |
13.00 |
|
|
EERd |
|
3.14 |
3.26 |
2.29 |
2.63 |
|
|
Power input |
kW |
2.17 |
2.92 |
5.28 |
4.95 |
|
B Condition (30°C - 27/19) |
Pdc |
kW |
5.10 |
7.00 |
8.92 |
9.58 |
|
|
EERd |
|
4.35 |
4.61 |
4.03 |
4.50 |
|
|
Power input |
kW |
1.17 |
1.52 |
2.21 |
2.13 |
|
C Condition (25°C - 27/19) |
Pdc |
kW |
3.40 |
4.50 |
5.74 |
6.16 |
|
|
EERd |
|
7.47 |
6.54 |
6.31 |
7.01 |
|
|
Power input |
kW |
0.46 |
0.69 |
0.91 |
0.88 |
|
D Condition (20°C - 27/19) |
Pdc |
kW |
2.89 |
3.11 |
3.18 |
3.74 |
|
|
EERd |
|
11.12 |
9.38 |
9.82 |
10.84 |
|
|
Power input |
kW |
0.26 |
0.33 |
0.32 |
0.35 |
Space heating (Average climate) |
Energy efficiency class |
|
A |
A |
|
|
|
Capacity |
Pdesign |
kW |
4.50 |
6.00 |
6.00 |
7.80 |
|
SCOP/A |
|
4.00 |
3.85 |
3.80 |
4.31 |
|
SCOPnet/A |
|
4.00 |
3.85 |
3.80 |
4.31 |
|
ηs,h |
% |
|
|
149 |
169 |
|
Annual energy consumption |
kWh/a |
1,575 |
2,182 |
2,211 |
2,534 |
|
Required back up heating cap at design conditions |
kW |
0.00 |
0.00 |
0.00 |
0.00 |
|
TOL |
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
-10 |
|
|
Pdh (declared heating cap) |
kW |
4.50 |
6.00 |
6.00 |
7.80 |
|
|
COPd (declared COP) |
|
2.31 |
2.33 |
2.43 |
2.26 |
|
|
Power input |
kW |
1.94 |
2.58 |
2.47 |
3.44 |
|
TBivalent |
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
-10 |
|
|
Pdh (declared heating cap) |
kW |
4.50 |
6.00 |
6.00 |
7.80 |
|
|
COPd (declared COP) |
|
2.31 |
2.33 |
2.43 |
2.26 |
|
|
Power input |
kW |
1.94 |
2.58 |
2.47 |
3.44 |
|
A Condition (-7°C) |
Pdh (declared heating cap) |
kW |
3.98 |
5.31 |
5.30 |
6.90 |
|
|
COPd (declared COP) |
|
2.31 |
2.54 |
2.61 |
2.60 |
|
|
Power input |
kW |
1.72 |
2.09 |
2.03 |
2.65 |
|
B Condition (2°C) |
Pdh (declared heating cap) |
kW |
2.42 |
3.23 |
3.23 |
4.20 |
|
|
COPd (declared COP) |
|
4.10 |
3.67 |
3.64 |
4.32 |
|
|
Power input |
kW |
0.59 |
0.88 |
0.89 |
0.97 |
|
C Condition (7°C) |
Pdh (declared heating cap) |
kW |
1.92 |
2.10 |
2.13 |
3.40 |
|
|
COPd (declared COP) |
|
5.32 |
5.16 |
4.88 |
5.92 |
|
|
Power input |
kW |
0.36 |
0.41 |
0.44 |
0.57 |
|
D Condition (12°C) |
Pdh (declared heating cap) |
kW |
2.29 |
2.50 |
2.55 |
3.99 |
|
|
COPd (declared COP) |
|
6.74 |
6.42 |
6.24 |
7.26 |
|
|
Power input |
kW |
0.34 |
0.39 |
0.41 |
0.55 |
Power consumption in other than active mode |
Thermostat-off mode |
PTO |
Heating |
W |
|
|
12 |
12 |
|
|
|
Cooling |
W |
|
|
0 |
0 |
|
Standby mode |
Cooling |
PSB |
W |
12 |
12 |
12 |
12 |
|
|
Heating |
PSB |
W |
12 |
12 |
12 |
12 |
|
Crankcase heater mode |
PCK |
W |
0 |
0 |
0 |
0 |
|
Off mode |
POFF |
W |
12 |
12 |
12 |
12 |
Pto (Thermostat off) |
W |
12, 0 |
12, 0 |
|
|
Indication if the heater is equipped with a supplementary heater (pair application) |
|
|
No |
No |
Cooling |
Cdc (Degradation cooling) |
|
0.25 |
0.25 |
0.25 |
0.25 |
Heating |
Cdh (Degradation heating) |
|
0.25 |
0.25 |
0.25 |
0.25 |
Cooling function included |
Yes |
Yes |
Yes |
Yes |
Heating function included |
Yes |
Yes |
Yes |
Yes |
Average climate included |
Yes |
Yes |
Yes |
Yes |
Cold season included |
No |
No |
No |
No |
Warm season included |
No |
No |
No |
No |
Ecolabel logo |
No |
No |
No |
No |
Notes |
(1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W] |
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m |
Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m |
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |