FXUQ71AVEB |
FXUQ100AVEB |
Dimensions |
Unit |
Height |
Mm |
198 |
198 |
|
|
Width |
Mm |
950 |
950 |
|
|
Depth |
Mm |
950 |
950 |
Weight |
Unit |
kg |
26 |
27 |
Casing |
Colour |
|
Fresh White |
Fresh White |
|
Material |
|
Resin |
Resin |
Refrigerant |
Type |
|
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
Piping connections |
Liquid |
Type |
|
Flare connection |
Flare connection |
|
|
OD |
Mm |
9.52 |
9.52 |
|
Gas |
Type |
|
Flare connection |
Flare connection |
|
|
OD |
Mm |
15.9 |
15.9 |
|
Drain |
|
I.D. 20/O.D. 26 |
I.D. 20/O.D. 26 |
Power supply |
Phase |
|
1~ |
1~ |
|
Frequency |
Hz |
50/60 |
50/60 |
|
Voltage |
V |
220-240/220-230 |
220-240/220-230 |
Current - 50Hz |
Maximum fuse amps (MFA) |
A |
16 |
16 |
Notes |
(1) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(1) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(2) - Maximum allowable voltage range variation between phases is 2%. |
(2) - Maximum allowable voltage range variation between phases is 2%. |
|
(3) - MCA/MFA: MCA = 1.25 x FLA |
(3) - MCA/MFA: MCA = 1.25 x FLA |
|
(4) - MFA ≤ 4 x FLA |
(4) - MFA ≤ 4 x FLA |
|
(5) - Next lower standard fuse rating minimum 16A |
(5) - Next lower standard fuse rating minimum 16A |
|
(6) - Select wire size based on the value of MCA |
(6) - Select wire size based on the value of MCA |
|
(7) - Instead of a fuse, use a circuit breaker |
(7) - Instead of a fuse, use a circuit breaker |
|
(8) - Contains fluorinated greenhouse gases |
(8) - Contains fluorinated greenhouse gases |