Specifications Table for RXP-M

RXP20M5V1B RXP25M5V1B RXP35M5V1B RXP50M5V1B RXP60M5V1B RXP71M5V1B RXP50M2V1B (Archived) RXP60M2V1B (Archived) RXP71M2V1B (Archived)
Sound pressure level Heating Nom. dBA 47 47 48 49 49 52 49 49 52
  Cooling Nom. dBA 46 46 48 47 49 52 47 49 52
Standard Accessories Drain plug 1 1 1 1 1 1 1 1 1
  Installation manual 1 1 1 1 1 1 1 1 1
  Refrigerant charge label 1 1 1 1 1 1 1 1 1
  Multilingual fluorinated greenhouse gases labels 1 1 1 1 1 1 1 1 1
  Drain cap (1)       6 6 6 6 6 6
  Drain cap (2)       3 3 3 3 3 3
Refrigerant GWP   675.0 675.0 675.0 675 675 675 675 675 675
  Charge kg 0.55 0.55 0.70 0.90 1.15 1.15 0.90 1.15 1.15
  Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
Operation range Cooling Ambient Max. °CDB 48 48 48 48 48 48 46 46 46
      Min. °CDB -10 -10 -10 -10 -10 -10 -10 -10 -10
Piping connections Level difference IU - OU Max. m 12 12 12 20 20 20 20 20 20
  Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m)
Dimensions Unit Width mm 658 658 658 870 870 870 870 870 870
    Depth mm 275 275 275 373 373 373 373 373 373
    Height mm 550 550 550 734 734 734 734 734 734
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Weight Unit kg 26 26 28 46.0 50.0 50.0 46.0 50.0 50.0
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240
Notes (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range (1) - See separate drawing for operation range
  (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data
  (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases
Standard Accessories General safety precautions 1 1 1