EBHQ006BBV3 |
EBHQ008BBV3 |
Heating capacity |
Nom. |
kW |
6.00 (2), 5.58 (4) |
8.85 (2), 8.15 (4) |
Cooling capacity |
Nom. |
kW |
7.00 (1), 5.12 (3) |
8.37 (1), 6.08 (3) |
Power input |
Cooling |
Nom. |
kW |
2.20 (1), 2.16 (3) |
2.97 (1), 2.75 (3) |
|
Heating |
Nom. |
kW |
1.41 (2), 1.79 (4) |
2.21 (2), 2.72 (4) |
COP |
4.26 (2), 3.11 (4) |
4.00 (2), 3.00 (4) |
EER |
3.18 (1), 2.37 (3) |
2.82 (1), 2.21 (3) |
Dimensions |
Unit |
Height |
Mm |
805 |
805 |
|
|
Width |
Mm |
1,190 |
1,190 |
|
|
Depth |
Mm |
360 |
360 |
Weight |
Unit |
kg |
95 |
95 |
|
Operation weight |
kg |
99 |
99 |
Sound power level |
Heating |
Nom. |
dBA |
61 |
62 |
|
Cooling |
Nom. |
dBA |
63 |
63 |
Sound pressure level |
Heating |
Nom. |
dBA |
48 (6) |
49 (6) |
|
Cooling |
Nom. |
dBA |
48 (6) |
50 (6) |
Refrigerant |
Type |
|
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
|
Charge |
kg |
1.7 |
1.7 |
|
Charge |
TCO2Eq |
3.5 |
3.5 |
Compressor component |
Main power supply |
Name |
|
V3 |
V3 |
|
|
Phase |
|
1~ |
1~ |
|
|
Frequency |
Hz |
50 |
50 |
|
|
Voltage |
V |
230 |
230 |
Notes |
(1) - Tamb 35°C - LWE 18°C (DT=5°C) |
(1) - Tamb 35°C - LWE 18°C (DT=5°C) |
|
(2) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) |
(2) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) |
|
(3) - Tamb 35°C - LWE 7°C (DT=5°C) |
(3) - Tamb 35°C - LWE 7°C (DT=5°C) |
|
(4) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(4) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
|
(5) - Pump power input is included in heating and cooling power input |
(5) - Pump power input is included in heating and cooling power input |
|
(6) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. |
(6) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. |
|
(7) - 15°C-25°C: BUH only, no heat pump operation = during commissioning |
(7) - 15°C-25°C: BUH only, no heat pump operation = during commissioning |
|
(8) - Including piping + PHE; excluding expansion vessel |
(8) - Including piping + PHE; excluding expansion vessel |
|
(9) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info. |
(9) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info. |
|
(10) - The 3-way valve should be mounted as close as possible to the outdoor unit |
(10) - The 3-way valve should be mounted as close as possible to the outdoor unit |
|
(11) - Power supply compressor compartment is for compressor, fan, pump and controller |
(11) - Power supply compressor compartment is for compressor, fan, pump and controller |
|
(12) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase |
(12) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase |
|
(13) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax |
(13) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax |
|
(14) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A |
(14) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A |
|
(15) - Wiring connections: cf. connection diagram for full wiring overview; Select diameter and type according to local regulations; For more details on voltage range and current cf. EBHQ installation manual |
(15) - Wiring connections: cf. connection diagram for full wiring overview; Select diameter and type according to local regulations; For more details on voltage range and current cf. EBHQ installation manual |
|
(16) - See separate drawing for operation range |
(16) - See separate drawing for operation range |
|
(17) - Contains fluorinated greenhouse gases |
(17) - Contains fluorinated greenhouse gases |
|
(17) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC |