EWAQ170E-XR |
EWAQ190E-XR |
EWAQ220E-XR |
EWAQ260E-XR |
EWAQ300E-XR |
EWAQ320E-XR |
Cooling capacity |
Nom. |
kW |
172.1 |
193.5 |
219.2 |
253.6 |
302.3 |
322.1 |
Capacity control |
Method |
|
Staged |
Staged |
Staged |
Staged |
Staged |
Staged |
|
Minimum capacity |
% |
50 |
43 |
25 |
33 |
22 |
23 |
Power input |
Cooling |
Nom. |
kW |
56.49 |
64.44 |
71.63 |
85.48 |
102.3 |
109.5 |
EER |
3.047 |
3.003 |
3.059 |
2.967 |
2.956 |
2.941 |
ESEER |
4.45 |
4.55 |
4.33 |
4.65 |
4.62 |
4.54 |
Dimensions |
Unit |
Depth |
Mm |
4,413 |
4,413 |
5,313 |
5,313 |
6,213 |
6,213 |
|
|
Height |
Mm |
2,271 |
2,271 |
2,271 |
2,271 |
2,271 |
2,271 |
|
|
Width |
Mm |
1,224 |
1,224 |
1,224 |
1,224 |
1,224 |
1,224 |
Weight |
Operation weight |
kg |
1,982 |
2,076 |
2,148 |
2,503 |
2,647 |
2,855 |
|
Unit |
kg |
1,970 |
2,064 |
2,134 |
2,489 |
2,632 |
2,840 |
Water heat exchanger |
Type |
|
Plate heat exchanger |
Plate heat exchanger |
Plate heat exchanger |
Plate heat exchanger |
Plate heat exchanger |
Plate heat exchanger |
|
Water volume |
l |
12 |
12 |
14 |
14 |
14 |
14 |
Air heat exchanger |
Type |
|
High efficiency fin and tube type |
High efficiency fin and tube type |
High efficiency fin and tube type |
High efficiency fin and tube type |
High efficiency fin and tube type |
High efficiency fin and tube type |
Fan |
Air flow rate |
Nom. |
l/s |
16,743 |
16,285 |
20,618 |
20,056 |
25,243 |
24,604 |
|
Speed |
rpm |
705 |
705 |
705 |
705 |
705 |
705 |
Compressor |
Quantity |
|
2 |
2 |
2 |
3 |
3 |
3 |
|
Type |
|
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Sound power level |
Cooling |
Nom. |
dBA |
85 |
86 |
87 |
86 |
88 |
89 |
Sound pressure level |
Cooling |
Nom. |
dBA |
66 |
67 |
68 |
67 |
68 |
69 |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,088 |
2,088 |
2,088 |
2,088 |
2,088 |
2,088 |
|
Circuits |
Quantity |
|
1 |
1 |
1 |
1 |
1 |
1 |
|
Charge |
kg |
28 |
31 |
27 |
35 |
43 |
53 |
Charge |
Per circuit |
TCO2Eq |
50.1 |
64.7 |
56.4 |
83.5 |
89.8 |
110.6 |
Power supply |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
Compressor |
Starting method |
|
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Direct on line |
Notes |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation. |
|
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
(2) - Sound pressure levels are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C; full load operation; Standard: ISO3744 |
|
(3) - Fluid: Water |
(3) - Fluid: Water |
(3) - Fluid: Water |
(3) - Fluid: Water |
(3) - Fluid: Water |
(3) - Fluid: Water |
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
|
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(5) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
|
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(6) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
|
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(7) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
|
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(8) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
|
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(9) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
|
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
(12) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding |
|
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
(13) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 |
|
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
(14) - Unit performances refer to ideal running conditions that are reproducible in laboratory test environment in accordance to recognized industry standards (i.e. EN14511) |
|
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
(15) - Weight and dimensions are indicative, for specific values refer to certified drawings issued by the factory |
|
(16) - For specific information about additional options refer to the options section in the data book |
(16) - For specific information about additional options refer to the options section in the data book |
(16) - For specific information about additional options refer to the options section in the data book |
(16) - For specific information about additional options refer to the options section in the data book |
(16) - For specific information about additional options refer to the options section in the data book |
(16) - For specific information about additional options refer to the options section in the data book |