Specifications Table for EWLD-I-SS

EWLD320I-SS EWLD400I-SS EWLD420I-SS EWLD500I-SS EWLD600I-SS EWLD650I-SS EWLD750I-SS EWLD800I-SS EWLD850I-SS EWLD900I-SS EWLD950I-SS EWLDC10I-SS EWLDC11I-SS EWLDC12I-SS EWLDC13I-SS EWLDC14I-SS EWLDC15I-SS EWLDC16I-SS EWLDC17I-SS
Sound pressure level Cooling Nom. dBA 75 (2) 76 (2) 78 (2) 78 (2) 78 (2) 78 (2) 79 (2) 80 (2) 81 (2) 81 (2) 81 (2) 80 (2) 80 (2) 81 (2) 81 (2) 83 (2) 83 (2) 83 (2) 83 (2)
Sound power level Cooling Nom. dBA 94 97 97 97 97 97 98 99 100 100 100 100 100 101 101 103 103 103 103
Refrigerant Circuits Quantity   1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3
  Charge kg 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
  Type   R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
Dimensions Unit Width mm 1,464 1,464 1,464 1,464 1,464 1,464 1,464 1,464 1,464 1,464 1,464 2,135 2,135 2,135 2,135 2,135 2,135 2,135 2,135
    Depth mm 3,114 3,114 3,114 3,114 4,391 4,391 4,391 4,391 4,391 4,391 4,391 4,426 4,426 4,426 4,426 4,426 4,426 4,426 4,426
    Height mm 1,899 1,899 1,899 1,899 2,325 2,325 2,325 2,325 2,325 2,325 2,325 2,415 2,415 2,415 2,415 2,415 2,415 2,415 2,415
Compressor Type   Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor
  Quantity   1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3
Capacity control Minimum capacity % 25.0 25.0 25.0 25.0 12.5 12.5 12.5 12.5 12.5 12.5 12.5 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3
  Method   Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless
Weight Operation weight kg 2,054 2,054 2,052 2,056 3,602 3,602 3,603 3,604 3,605 3,645 3,645 5,667 5,671 5,671 5,677 5,680 5,680 5,680 5,680
  Unit kg 1,861 1,861 1,869 1,884 3,331 3,339 3,347 3,356 3,364 3,412 3,412 5,146 5,167 5,167 5,188 5,208 5,208 5,208 5,208
Water heat exchanger - evaporator Type   Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube
Cooling capacity Nom. kW 315 (1) 374 (1) 437 (1) 509 (1) 607 (1) 670 (1) 740 (1) 802 (1) 865 (1) 935 (1) 975 (1) 1,029 (1) 1,097 (1) 1,144 (1) 1,210 (1) 1,278 (1) 1,330 (1) 1,381 (1) 1,433 (1)
EER 3.93 (1) 3.89 (1) 3.88 (1) 3.79 (1) 3.80 (1) 3.82 (1) 3.86 (1) 3.86 (1) 3.86 (1) 3.81 (1) 3.69 (1) 3.64 (1) 3.83 (1) 3.79 (1) 3.80 (1) 3.80 (1) 3.74 (1) 3.68 (1) 3.63 (1)
Piping connections Discharge line connection mm 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9
Power input Cooling Nom. kW 80.3 (1) 96.0 (1) 113 (1) 134 (1) 160 (1) 175 (1) 192 (1) 208 (1) 224 (1) 246 (1) 264 (1) 283 (1) 286 (1) 302 (1) 318 (1) 336 (1) 356 (1) 375 (1) 395 (1)
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Notes (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation.
  (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744. (2) - Sound level data are measured at entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C; full load operation; standard: ISO3744.
  (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water
  (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load
  (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
  (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope
  (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1