Specifications Table for EWYK-QZ

EWYK100QZXSA2 EWYK135QZXSA2
Cooling capacity Nom. kW 91.3 128.30
Capacity control Method   Inverter controlled Inverter controlled
  Minimum capacity % 15 11
Power input Cooling Nom. kW 30.43 48.42
EER 3.00 2.65
IPLV 6.24 5.94
SEER 5.06 4.81
Dimensions Unit Depth mm 1207 1207
    Height mm 2382 2382
    Width mm 2653 2653
Weight Operation weight kg 1195 1272
  Unit kg 1166 1239
Casing Colour   Ivory white Ivory white
  Material   Galvanized and painted steel sheet Galvanized and painted steel sheet
Air heat exchanger Type   Al Fins & Cu Tubes Al Fins & Cu Tubes
Fan Quantity   2 2
  Type   Axial Axial
  Air flow rate Cooling Nom. l/s 12600 14160
Fan motor Drive   Brushless Brushless
Compressor Quantity   2 2
  Type   Scroll Scroll
Operation range Air side Cooling Min. °CDB -20 -20
      Max. °CDB 46 46
  Water side Evaporator Min. °CDB 20 20
      Max. °CDB 75 75
Sound power level Cooling Nom. dBA 86.3 90.9
Sound pressure level Cooling Nom. dBA 68.1 72.7
Refrigerant Type   R-290 R-290
  GWP   0.02 0.02
  Charge kg 6.3 6.6
  Circuits Quantity   2 2
Piping connections Evaporator water inlet/outlet (OD)   3" 3"
Power supply Phase   3 3
  Frequency Hz 50 50
  Voltage V 400 400
  Voltage range Min. % -10 -10
    Max. % 10 10
Unit Starting current Max A 0 0
  Running current Cooling Nom. A 52.1 82.8
    Max A 122.0 142.0
  Max unit current for wires sizing A 134.0 156.0
Notes (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
  (2) - Condition: outdoor temp. 7°CDB, 6°CWB; LWC 35°C (DT = 5°C) (2) - Condition: outdoor temp. 7°CDB, 6°CWB; LWC 35°C (DT = 5°C)
  (3) - According to EN14825 (3) - According to EN14825
  (4) - Depends on operation mode, refer to installation manual. (4) - Depends on operation mode, refer to installation manual.
  (5) - For more details, see operation range drawing (5) - For more details, see operation range drawing
  (6) - Performance data calculated as Chiller Configurator - 2.0.0 (6) - Performance data calculated as Chiller Configurator - 2.0.0