FCAHG71GVEB / RZQSG71L3V1B FCAHG125GVEB / RZQSG125L9V1B FCAHG140GVEB / RZQSG140L9V1B
Cooling capacity Nom. kW 6.80 (1) 12.0 (1) 13.4 (1)
Space cooling SEER   6.50 5.40
  Annual energy consumption kWh/a 367 778
  Capacity Pdesign kW 6.80 12.0
  Energy efficiency class   A++ A
Space heating (Average climate) Capacity Pdesign kW 7.60 8.03
  SCOP/A   4.15 4.10
  Energy efficiency class   A+ A+
  Annual energy consumption kWh/a 2,563 2,742
Nominal efficiency EER   3.50 (3) 3.23 (3) 3.11 (3)
  Annual energy consumption kWh 970 1,855
  COP   4.10 (3) 3.75 (3) 3.61 (3)
  Energy labeling Directive Cooling   A A
    Heating   A A
Heating capacity Nom. kW 7.50 (2) 13.5 (2) 15.5 (2)
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only