RKXYQ8T7Y1B |
RKXYQ5T7Y1B (Archived) |
Sound pressure level
|
Cooling
|
Nom.
|
dBA
|
48.0 (5)
|
47.0 (5)
|
Standard Accessories
|
Installation and operation manual
|
1
|
1
|
|
Connection pipes
|
5
|
4
|
|
Declaration of conformity
|
1
|
1
|
|
Refrigerant label for F-gas regulation
|
1
|
1
|
|
Tie-wraps
|
3
|
3
|
|
Screws
|
1
|
1
|
Compressor
|
Type
|
|
Hermetically sealed scroll compressor
|
Hermetically sealed swing compressor
|
Weight
|
Unit
|
kg
|
105
|
77
|
Refrigerant
|
GWP
|
|
2,087.5
|
2,087.5
|
|
Charge
|
kg
|
4.00
|
2.00
|
|
Type
|
|
R-410A
|
R-410A
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
64.0 (4)
|
60.0 (4)
|
Dimensions
|
Unit
|
Width
|
mm
|
760
|
600
|
|
|
Depth
|
mm
|
554
|
554
|
|
|
Height
|
mm
|
701
|
701
|
Power supply
|
Phase
|
|
3N~
|
3N~
|
|
Name
|
|
Y1
|
Y1
|
|
Frequency
|
Hz
|
50
|
50
|
|
Voltage
|
V
|
380-415
|
380-415
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
|
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(6) - Refer to refrigerant pipe selection or installation manual
|
(6) - Refer to refrigerant pipe selection or installation manual
|
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
|
(12) - TOCA means the total value of each OC set.
|
(12) - TOCA means the total value of each OC set.
|
|
(13) - FLA means the nominal running current of the fan
|
(13) - FLA means the nominal running current of the fan
|
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(16) - Sound values are measured in a semi-anechoic room.
|
(16) - Sound values are measured in a semi-anechoic room.
|
|
(17) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(17) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
|
(18) - Ssc: Short-circuit power
|
(18) - Ssc: Short-circuit power
|
|
(19) - For detailed contents of standard accessories, see installation/operation manual
|
(19) - For detailed contents of standard accessories, see installation/operation manual
|