| RZAG71M7Y1B | RZAG100M7Y1B | RZAG125M7Y1B | RZAG140M7Y1B | |||||
|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Heating | Nom. | dBA | 51 | 52 | 52 | ||
| Cooling | Nom. | dBA | 47 | 50 | 51 | |||
| Standard Accessories | Tie-wraps | 2 | 2 | 2 | 2 | |||
| Installation manual | 1 | 1 | 1 | 1 | ||||
| Refrigerant label for F-gas regulation | 1 | 1 | 1 | 1 | ||||
| General safety precautions | 1 | 1 | 1 | 1 | ||||
| LOT10 Energy Label | 1 | 1 | 1 | 1 | ||||
| Refrigerant | Charge | TCO2Eq | 2.53 | 2.53 | 2.53 | |||
| GWP | 675 | 675 | 675 | |||||
| Charge | kg | 3.75 | 3.75 | 3.75 | ||||
| Type | R-32 | R-32 | R-32 | |||||
| Piping connections | Liquid | OD | mm | 9.52 | 9.52 | 9.52 | ||
| Piping length | OU - IU | Max. | m | 85 | 85 | 85 | ||
| System | Chargeless | m | 40 | 40 | 40 | |||
| Equivalent | m | 100 | 100 | 100 | ||||
| Gas | OD | mm | 15.9 | 15.9 | 15.9 | |||
| Level difference | IU - IU | Max. | m | 0.5 | 0.5 | 0.5 | ||
| IU - OU | Max. | m | 30.0 | 30.0 | 30.0 | |||
| Additional refrigerant charge | kg/m | See installation manual | See installation manual | See installation manual | ||||
| Sound power level | Cooling | dBA | 66 | 69 | 70 | |||
| Heating | dBA | 69 (1) | 70 (1) | |||||
| Dimensions | Unit | Width | mm | 940 | 940 | 940 | ||
| Depth | mm | 320 | 320 | 320 | ||||
| Height | mm | 1,430 | 1,430 | 1,430 | ||||
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed swing compressor | Hermetically sealed swing compressor | ||||
| Weight | Unit | kg | 92 | 92 | 92 | |||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 16 | 16 | 16 | |||
| Power supply | Phase | 3~ | 3~ | 3~ | ||||
| Frequency | Hz | 50 | 50 | 50 | ||||
| Voltage | V | 380-415 | 380-415 | 380-415 | ||||
| Notes | (1) - According to ENER Lot 21 | (1) - According to ENER Lot 21 | (1) - According to ENER Lot 21 | |||||
| (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. | (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. | (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. | ||||||
| (3) - Ssc: Short-circuit power | (3) - Ssc: Short-circuit power | (3) - Ssc: Short-circuit power | ||||||
| (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. | (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. | (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. | ||||||
| Dimensions | Unit | Height | mm | 990 | ||||
| Width | mm | 940 | ||||||
| Depth | mm | 320 | ||||||
| Weight | Unit | kg | 70 | |||||
| Compressor | Type | Hermetically sealed swing compressor | ||||||
| Operation range | Cooling | Ambient | Min. | °CDB | -20 | |||
| Max. | °CDB | 52 | ||||||
| Heating | Ambient | Min. | °CWB | -20 | ||||
| Max. | °CWB | 18.0 | ||||||
| Sound power level | Cooling | dBA | 65 | |||||
| Sound pressure level | Cooling | Nom. | dBA | 46 | ||||
| Heating | Nom. | dBA | 49 | |||||
| Refrigerant | Type | R-32 | ||||||
| Charge | kg | 2.95 | ||||||
| GWP | 675 | |||||||
| Charge | tCO2Eq | 1.99 | ||||||
| Piping connections | Liquid | OD | mm | 9.52 | ||||
| Gas | OD | mm | 15.9 | |||||
| Piping length | OU - IU | Max. | m | 55 | ||||
| System | Equivalent | m | 75 | |||||
| Chargeless | m | 40 | ||||||
| Additional refrigerant charge | kg/m | See installation manual | ||||||
| Level difference | IU - OU | Max. | m | 30.0 | ||||
| IU - IU | Max. | m | 0.5 | |||||
| Power supply | Phase | 3~ | ||||||
| Frequency | Hz | 50 | ||||||
| Voltage | V | 380-415 | ||||||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 16 | |||||