Specifications Table for RZQG-L9V1

RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L9V1B RZQG71L9V1B_AMB
Sound pressure level Heating High dBA         12
    Nom. dBA 52 53 53 50 50
    Low dBA         12
  Cooling Low dBA         12
    High dBA         12
    Nom. dBA 50 51 52 48 48
  Night quiet mode Taso 1 dBA 45 45 45 43 43
Standard Accessories Tie-wraps 2 2 2 2
  Installation manual 1 1 1 1
Refrigerant Refrigerant-=-Charge-=-TCO2Eq TCO2Eq 8.35 8.35 8.35 6.05 6.1
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg 4.0 4.0 4.0 2.9 2.9
  Type   R-410A R-410A R-410A R-410A R-410A
Fan motor Output W         94
  Speed Cooling Super low rpm         12
    Heating Super low rpm         12
Operation range Jäähdytys Ympäristö Maks. °CDB 50.0 50.0 50.0 50.0 50
      Min. °CDB -15.0 -15.0 -15.0 -15.0 -15
  Lämmitys Ympäristö Max. °CWB 15.5 15.5 15.5 15.5 15.5
      Min. °CWB -20.0 -20.0 -20.0 -20.0 -20
Piping connections Liquid OD mm 9.52 9.52 9.52 9.52
  Piping length OU - IU Max. m 75 75 75 50
    System Chargeless m 30 30 30 30
      Equivalent m 90 90 90 70
  Gas OD mm 15.9 15.9 15.9 15.9
  Level difference IU - IU Max. m 0.5 0.5 0.5 0.5
    IU - OU Max. m 30.0 30.0 30.0 30.0
  Additional refrigerant charge kg/m See installation manual See installation manual See installation manual See installation manual
Sound power level Cooling dBA 66.0 67.0 69.0 64.0 64
  Heating dBA 66.0 67.0 69.0 64.0 12
Capacity control step %         100-0
Dimensions Unit Width mm 940 940 940 940 940
    Depth mm 320 320 320 320 320
    Height mm 1,430 1,430 1,430 990 990
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Weight Unit kg 95.0 95.0 95.0 69.0 69
Fan Air flow rate Heating Super low cfm         12.000
      Super low m³/min         12.000
    Cooling Super low m³/min         12.000
      Super low cfm         12.000
Virta - 50 Hz Maximum fuse amps (MFA) A 40 40 40 25
Power supply Phase   1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240 220-240
Notes (1) - 3 with re-charging (1) - 3 with re-charging (1) - 3 with re-charging (1) - 3 with re-charging (1) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
  (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - 3 with re-charging
  (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase
  (4) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (4) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (4) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (4) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (4) - See separate drawing for electrical data
  (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data (5) - Contains fluorinated greenhouse gases
  (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
Piping connections Level difference IU - IU Max. m         0.5
    IU - OU Max. m         30.0
  Additional refrigerant charge kg/m         See installation manual
  Total piping length System Actual m         12