Specifications Table for UATYA-BFC3Y1

UATYA25BFC3Y1 UATYA30BFC3Y1 UATYA40BFC3Y1 UATYA50BFC3Y1 UATYA60BFC3Y1 UATYA70BFC3Y1 UATYA80BFC3Y1 UATYA90BFC3Y1 UATYA100BFC3Y1 UATYA110BFC3Y1 UATYA120BFC3Y1 UATYA140BFC3Y1 UATYA150BFC3Y1 UATYA160BFC3Y1 UATYA180BFC3Y1 UATYA190BFC3Y1
Cooling capacity Nom. kW   31.3 (1) 38.7 (1) 45.7 (1)   65.3 (1) 74.8 (1) 89.8 (1) 95.8 (1) 108.9 (1) 115.0 (1) 133.4 (1) 144.7 (1) 154.6 (1) 171.9 (1) 187.0 (1)
  With 30% fresh air kW   33.9 (1) 42.5 (1) 49.6 (1)   70.5 (1) 81.3 (1) 96.8 (1) 104.3 (1) 118.0 (1) 124.5 (1) 145.6 (1) 156.8 (1) 168.3 (1) 186.5 (1) 204.4 (1)
Heating capacity Nom. kW   29.5 (2) 36.3 (2) 46.2 (2)   64.9 (2) 68.5 (2) 84.2 (2) 92.8 (2) 101.5 (2) 108.0 (2) 123.1 (2) 136.4 (2) 147.1 (2) 157.1 (2) 176.9 (2)
  With 30% fresh air kW   31.0 (2) 38.3 (2) 47.7 (2)   68.6 (2) 71.6 (2) 87.2 (2) 97.9 (2) 107.0 (2) 112.3 (2) 132.0 (2) 147.5 (2) 160.0 (2) 173.5 (2) 191.6 (2)
Power input Cooling Nom. kW   10.1 (1) 12.7 (1) 15.4 (1)   22.4 (1) 24.2 (1) 29.4 (1) 32.3 (1) 36.4 (1) 39.5 (1) 42.5 (1) 47.9 (1) 50.7 (1) 56.1 (1) 62.9 (1)
  Heating Nom. kW   8.9 (2) 11.1 (2) 14.2 (2)   20.2 (2) 20.3 (2) 26.1 (2) 29.0 (2) 30.3 (2) 33.2 (2) 35.8 (2) 40.9 (2) 45.1 (2) 47.2 (2) 54.2 (2)
EER 2.83 (1), 2.96 (3) 3.09 (1), 3.20 (3) 3.06 (1), 3.27 (3) 2.96 (1), 3.12 (3) 3.12 (1), 3.23 (3) 2.92 (1), 3.00 (3) 3.09 (1), 3.21 (3) 3.06 (1), 3.22 (3) 2.97 (1), 3.14 (3) 2.99 (1), 3.11 (3) 2.91 (1), 3.01 (3) 3.14 (1), 3.26 (3) 3.02 (1), 3.14 (3) 3.05 (1), 3.18 (3) 3.07 (1), 3.21 (3) 2.97 (1), 3.14 (3)
COP 3.22 (2), 3.41 (3) 3.31 (2), 3.50 (3) 3.26 (2), 3.51 (3) 3.24 (2), 3.46 (3) 3.25 (2), 3.40 (3) 3.21 (2), 3.39 (3) 3.37 (2), 3.56 (3) 3.22 (2), 3.45 (3) 3.20 (2), 3.42 (3) 3.35 (2), 3.57 (3) 3.25 (2), 3.40 (3) 3.44 (2), 3.62 (3) 3.33 (2), 3.57 (3) 3.26 (2), 3.49 (3) 3.33 (2), 3.63 (3) 3.27 (2), 3.50 (3)
Space cooling Capacity Pdesign kW   31.3 38.7 45.7   65.3 74.8 89.8 95.8 108.9 115.0 133.4 144.7 154.6 171.9 187.0
  SEER     4.79 (4) 5.39 (4) 5.26 (4)   4.53 (4) 5.56 (4) 5.47 (4) 5.17 (4) 5.29 (4) 5.15 (4) 4.38 (4) 4.26 (4) 4.27 (4) 4.15 (4) 4.08 (4)
Space heating (Average climate) Capacity Pdesign kW   29.5 36.3 46.2   64.9 68.5 84.2 92.8 101.5 108.0 123.1 136.4 147.1 157.1 176.9
  SCOP/A     3.38 (4) 3.67 (4) 3.65 (4)   3.41 (4) 3.70 (4) 3.65 (4) 3.62 (4) 3.56 (4) 3.53 (4) 3.39 (4) 3.36 (4) 3.34 (4) 3.31 (4) 3.34 (4)
Evaporator Supply side Fan Air flow rate m³/h   5,800 7,500 9,000   13,000 14,500 16,500 18,000 19,800 21,600 25,000 26,500 28,000 30,500 31,500
      High ESP Pa   727 (5) 510 (5) 439 (5)   410 (5) 526 (5) 493 (5) 463 (5) 427 (5) 394 (5) 441 (5) 416 (5) 388 (5) 340 (5) 310 (5)
      Nominal ESP Pa   300 (5) 300 (5) 300 (5)   300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5)
  Return side Fan Air flow rate m³/min   5,800 7,500 9,000   13,000 14,500 16,500 18,000 19,800 21,600 25,000 26,500 28,000 30,500 31,500
      High ESP Pa   352 (5) 561 (5) 519 (5)   474 (5) 596 (5) 543 (5) 519 (5) 483 (5) 438 (5) 324 (5) 445 (5) 353 (5) 497 (5) 428 (5)
      Nominal ESP Pa   300 (5) 300 (5) 300 (5)   300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5)
  Fresh air Ratio Standard %   30 30 30   30 30 30 30 30 30 30 30 30 30 30
      In free cooling %   100 100 100   100 100 100 100 100 100 100 100 100 100 100
Operation range Cooling Min. °CDB   -10 -10 -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    Max. °CDB   48 48 48   48 48 48 48 48 48 48 48 48 48 48
  Heating Min. °CWB   -15 -15 -15   -15 -15 -15 -15 -15 -15 -15 -15 -15 -15 -15
    Max. °CWB   26 26 26   26 26 26 26 26 26 26 26 26 26 26
Condenser Air flow rate Cooling m³/h   16,038 16,374 16,341   32,203 35,774 37,285 36,195 38,143 36,865 70,704 72,395 67,733 70,200 72,005
  Refrigerant GWP     675 675 675   675 675 675 675 675 675 675 675 675 675 675
    Charge kg   10.0 12.0 15.0   18.0 23.0 24.0 28.0 30.0 36.0 38.0 38.0 46.0 50.0 50.0
Dimensions Unit Height mm   1,924 2,374 2,374   1,924 2,374 2,374 2,374 2,374 2,374 2,374 2,374 2,374 2,374 2,374
    Width mm   2,250 2,250 2,250   2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250
    Depth mm   3,514 3,514 3,514   6,317 6,317 6,317 6,317 6,317 6,317 7,117 7,117 7,117 7,117 7,117
Weight Unit kg   1,196 1,310 1,329   2,094 2,336 2,382 2,452 2,548 2,558 3,024 3,035 3,074 3,192 3,271
Sound pressure level Cooling dBA   66.0 (6) 68.0 (6) 67.3 (6)   68.1 (6) 72.6 (6) 68.7 (6) 69.9 (6) 70.6 (6) 74.2 (6) 68.3 (6) 68.3 (6) 68.7 (6) 69.1 (6) 70.0 (6)
Sound power level Cooling dBA   84.3 (7) 86.8 (7) 86.1 (7)   87.5 (7) 92.5 (7) 88.6 (7) 89.8 (7) 90.5 (7) 94.1 (7) 88.6 (7) 88.6 (7) 89.0 (7) 89.3 (7) 90.2 (7)
Power supply Name     400/3/50±5% 400/3/50±5% 400/3/50±5%   400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5%
  Phase     3~ 3~ 3~   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz   50 50 50   50 50 50 50 50 50 50 50 50 50 50
  Voltage V   400 400 400   400 400 400 400 400 400 400 400 400 400 400
Current Recommended fuses A   40 40 50   63 80 100 100 100 100 160 160 160 200 200
Notes (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018
  (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018
  (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air
  (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019
  (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters.
  (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level
  (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version
Operation range Heating Max. °CWB 26       26
    Min. °CWB -15       -15
  Cooling Max. °CDB 48       48
    Min. °CDB -10       -10
Cooling capacity Nom. kW 24.1 (1)       58.8 (1)
  With 30% fresh air kW 26.0 (1)       63.7 (1)
Heating capacity Nom. kW 24.0 (2)       55.1 (2)
  With 30% fresh air kW 25.0 (2)       57.1 (2)
Power input Cooling Nom. kW 8.5 (1)       18.8 (1)
  Heating Nom. kW 7.5 (2)       16.9 (2)
Space cooling Capacity Pdesign kW 24.1       58.8
  SEER   4.52 (4)       5.50 (4)
Space heating (Average climate) Capacity Pdesign kW 24.0       55.1
  SCOP/A   3.35 (4)       3.47 (4)
Evaporator Supply side Fan Air flow rate m³/h 4500       11000
      Nominal ESP Pa 300 (5)       300 (5)
      High ESP Pa 425 (5)       629 (5)
  Return side Fan Air flow rate m³/min 4500       11000
      Nominal ESP Pa 300 (5)       300 (5)
      High ESP Pa 461 (5)       426 (5)
  Fresh air Ratio Standard % 30       30
      In free cooling % 100       100
Condenser Air flow rate Cooling m³/h 15725       31183
  Refrigerant GWP   675       675
    Charge tCO2Eq 4725       12150
    Charge kg 7.0       18.0
Dimensions Unit Height mm 1924       1924
    Width mm 2250       2250
    Depth mm 3514       6317
Weight Unit kg 1166       1996
Sound pressure level Cooling dBA 63.9 (6)       69.0 (6)
Sound power level Cooling dBA 82.2 (7)       88.5 (7)
Power supply Name   400/3/50±5%       400/3/50±5%
  Phase   3~       3~
  Frequency Hz 50       50
  Voltage V 400       400
Current Recommended fuses A 25       50