Specifications Table for RQYQ-P

RQYQ10PY1 RQYQ12PY1 RQYQ140PY1 RQYQ14PY1 RQYQ16PY1 RQYQ18PY1 RQYQ20PY1 RQYQ22PY1 RQYQ24PY1 RQYQ26PY1 RQYQ28PY1 RQYQ30PY1 RQYQ32PY1 RQYQ34PY1 RQYQ36PY1 RQYQ38PY1 RQYQ40PY1 RQYQ42PY1 RQYQ44PY1 RQYQ46PY1 RQYQ48PY1 RQYQ8PY1
Sound pressure level Cooling Nom. dBA 58.0 60.0   60.0 60.0 61 62 63 63 63 63 63 63 64 64 65 65 65 65 65 65 57.0
Standard Accessories Installation manual Installation manual Installation manual Installation manual Installation manual Installation manual                                 Installation manual
  Operation manual Operation manual Operation manual Operation manual Operation manual Operation manual                                 Operation manual
  Connection pipes Connection pipes Connection pipes   Connection pipes Connection pipes                                 Connection pipes
  Clamps Clamps Clamps Clamps Clamps Clamps                                 Clamps
Capacity range HP 10 12 5 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 8
Operation range Jäähdytys Max. °CDB 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43
    Min. °CDB -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5
  Lämmitys Min. °CWB -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
    Max. °CWB 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5
Maximum number of connectable indoor units 21 26 10 30 34 39 43 47 52 56 60 64 64 64 64 64 64 64 64 64 64 17
Space cooling B Condition (30°C - 27/19) Pdc kW     10.3
    EERd       4.40
  D Condition (20°C - 27/19) Pdc kW     5.01
    EERd       9.29
  A Condition (35°C - 27/19) EERd       2.54
    Pdc kW     14.0
  C Condition (25°C - 27/19) EERd       7.31
    Pdc kW     6.63
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor                                 Hermetically sealed scroll compressor
Weight Unit kg 284 284 175 381 381                                 230
Refrigerant Refrigerant-=-Charge-=-TCO2Eq TCO2Eq 24.4 24.4 23.2 24.4 24.4                                 22.5
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg 11.7 11.7 11.1 11.7 11.7                                 10.8
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Järjestelmä Outdoor unit module 2             RQYQ10P RQYQ12P RQYQ12P RQYQ12P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ10P RQYQ10P RQYQ12P RQYQ12P RQYQ16P RQYQ16P RQYQ16P RQYQ16P
  Outdoor unit module 3                             RQYQ14P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P
  Outdoor unit module 1   RQYQ10P RQYQ12P RQYQ140P RQYQ14P RQYQ16P RQYQ8P RQYQ8P RQYQ10P RQYQ12P RQYQ10P RQYQ12P RQYQ14P RQYQ16P RQYQ10P RQYQ10P RQYQ10P RQYQ12P RQYQ10P RQYQ12P RQYQ14P RQYQ16P RQYQ8P
Indoor index connection Nom.   250 300 125 350 400 450 500 550 600 650 700 750 800 850 900 950 1,000 1,050 1,100 1,150 1,200 200
  Min.   125 150 62.5 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 100
  Max.   325 390 162.5 455 520 585 650 715 780 845 910 975 1,040 1,105 1,170 1,235 1,300 1,365 1,430 1,495 1,560 260
Cooling capacity Prated,c kW     14.0
Recommended combination     4 x FXSQ32A2VEB
Space heating (Average climate) TOL COPd (declared COP)       1.92
    Pdh (declared heating cap) kW     8.5
  D Condition (12°C) Pdh (declared heating cap) kW     4.18
    COPd (declared COP)       6.43
  B Condition (2°C) COPd (declared COP)       3.42
    Pdh (declared heating cap) kW     4.58
  C Condition (7°C) COPd (declared COP)       4.84
    Pdh (declared heating cap) kW     3.29
  A Condition (-7°C) COPd (declared COP)       2.20
    Pdh (declared heating cap) kW     7.52
  TBivalent Pdh (declared heating cap) kW     8.5
    Tbiv (bivalent temperature) °C     -10
    COPd (declared COP)       1.92
Piping connections Liquid OD mm 9.52 12.7 9.52 12.7 12.7 15.9 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 9.52
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
  Gas OD mm 22.2 28.6 15.9 28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3 19.1
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Level difference OU - IU Outdoor unit in highest position m 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
      Indoor unit in highest position m 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
    IU - IU Max. m 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Sound power level Cooling Nom. dBA     79
Dimensions Unit Width mm 930 930 635 1,240 1,240                                 930
    Depth mm 765 765 765 765 765                                 765
    Height mm 1,680 1,680 1,680 1,680 1,680                                 1,680
Fan External static pressure Max. Pa 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78
Heating capacity Prated,h kW     16.0
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - TOCA means the total value of each OC set. (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - MSC means the maximum current during start up of the compressor (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set.
  (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor
  (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Select wire size based on the value of MCA or TOCA. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%.
  (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the larger value of MCA or TOCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA
  (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases                   (11) - Contains fluorinated greenhouse gases