| RQEQ140PY13 | RQEQ180PY13 | RQEQ212PY13 | ||||
|---|---|---|---|---|---|---|
| Standard Accessories | Installation manual | Installation manual | Installation manual | Installation manual | ||
| Operation manual | Operation manual | Operation manual | Operation manual | |||
| Clamps | Clamps | Clamps | Clamps | |||
| Operation range | Cooling | Max. | °CDB | 43 | 43 | 43 |
| Min. | °CDB | -5 | -5 | -5 | ||
| Heating | Min. | °CWB | -20 | -20 | -20 | |
| Max. | °CWB | 15.5 | 15.5 | 15.5 | ||
| Space cooling | B Condition (30°C - 27/19) | Pdc | kW | 10.3 | 13.3 | 14.7 |
| EERd | 4.40 | 3.86 | 3.63 | |||
| D Condition (20°C - 27/19) | Pdc | kW | 5.01 | 4.94 | 4.95 | |
| EERd | 9.29 | 9.54 | 9.64 | |||
| A Condition (35°C - 27/19) | EERd | 2.54 | 2.22 | 1.74 | ||
| Pdc | kW | 14.0 | 18.0 | 20.0 | ||
| C Condition (25°C - 27/19) | EERd | 7.31 | 6.89 | 6.57 | ||
| Pdc | kW | 6.63 | 8.53 | 9.47 | ||
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | ||
| Weight | Unit | kg | 175 | 175 | 179 | |
| Refrigerant | Charge | TCO2Eq | 21.5 | 22.1 | 23.4 | |
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | |||
| Charge | kg | 10.3 | 10.6 | 11.2 | ||
| Type | R-410A | R-410A | R-410A | |||
| Cooling capacity | Prated,c | kW | 14.0 | 18.0 | 20.0 | |
| Nom. | kW | 14.0 (1) | 18.0 (1) | 21.2 (1) | ||
| Space heating (Average climate) | TOL | COPd (declared COP) | 1.92 | 1.84 | 1.64 | |
| Pdh (declared heating cap) | kW | 8.5 | 10.6 | 11.9 | ||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 4.18 | 4.40 | 4.44 | |
| COPd (declared COP) | 6.43 | 6.82 | 6.88 | |||
| B Condition (2°C) | COPd (declared COP) | 3.42 | 3.56 | 3.92 | ||
| Pdh (declared heating cap) | kW | 4.58 | 5.72 | 6.41 | ||
| C Condition (7°C) | COPd (declared COP) | 4.84 | 5.26 | 5.40 | ||
| Pdh (declared heating cap) | kW | 3.29 | 3.68 | 4.12 | ||
| A Condition (-7°C) | COPd (declared COP) | 2.20 | 2.22 | 2.20 | ||
| Pdh (declared heating cap) | kW | 7.52 | 9.40 | 10.5 | ||
| TBivalent | Pdh (declared heating cap) | kW | 8.5 | 10.6 | 11.9 | |
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | ||
| COPd (declared COP) | 1.92 | 1.84 | 1.64 | |||
| Piping connections | Liquid | OD | mm | 9.52 | 9.52 | 9.52 |
| Type | Braze connection | Braze connection | Braze connection | |||
| Gas | OD | mm | 15.9 | 19.1 | 19.1 | |
| Type | Braze connection | Braze connection | Braze connection | |||
| Discharge gas | OD | mm | 12.7 | 15.9 | 15.9 | |
| Type | Braze connection | Braze connection | Braze connection | |||
| Sound power level | Cooling | Nom. | dBA | 79 | 83 | 87 |
| Dimensions | Unit | Width | mm | 635 | 635 | 635 |
| Depth | mm | 765 | 765 | 765 | ||
| Height | mm | 1,680 | 1,680 | 1,680 | ||
| Heating capacity | Prated,h | kW | 16.0 | 20.0 | 22.4 | |
| Nom. | kW | 16.0 (2) | 20.0 (2) | 22.4 (2) | ||
| Power supply | Phase | 3~ | 3~ | 3~ | ||
| Name | Y1 | Y1 | Y1 | |||
| Frequency | Hz | 50 | 50 | 50 | ||
| Voltage | V | 380-415 | 380-415 | 380-415 | ||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | |||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | ||||
| (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. | (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. | (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. | ||||
| (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | ||||
| (5) - TOCA means the total value of each OC set. | (5) - TOCA means the total value of each OC set. | (5) - TOCA means the total value of each OC set. | ||||
| (6) - MSC means the maximum current during start up of the compressor | (6) - MSC means the maximum current during start up of the compressor | (6) - MSC means the maximum current during start up of the compressor | ||||
| (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | ||||
| (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | ||||
| (9) - Select wire size based on the larger value of MCA or TOCA | (9) - Select wire size based on the larger value of MCA or TOCA | (9) - Select wire size based on the larger value of MCA or TOCA | ||||
| (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | ||||
| (11) - Contains fluorinated greenhouse gases | (11) - Contains fluorinated greenhouse gases | (11) - Contains fluorinated greenhouse gases | ||||