|
RQYQ140PY1 |
RQYQ18PY1 |
RQYQ22PY1 |
RQYQ24PY1 |
RQYQ30PY1 |
RQYQ26PY1 |
RQYQ36PY1 |
RQYQ28PY1 |
RQYQ42PY1 |
RQYQ34PY1 |
RQYQ8PY1 |
RQYQ38PY1 |
RQYQ46PY1 |
RQYQ48PY1 |
RQYQ20PY1 |
RQYQ32PY1 |
RQYQ40PY1 |
RQYQ44PY1 |
RQYQ10PY1 |
RQYQ12PY1 |
RQYQ14PY1 |
RQYQ16PY1 |
System |
Outdoor unit module 1 |
|
RQYQ140P |
RQYQ8P |
RQYQ10P |
RQYQ12P |
RQYQ14P |
RQYQ10P |
RQYQ10P |
RQYQ12P |
RQYQ10P |
RQYQ10P |
RQYQ8P |
RQYQ10P |
RQYQ14P |
RQYQ16P |
RQYQ8P |
RQYQ16P |
RQYQ12P |
RQYQ12P |
RQYQ10P |
RQYQ12P |
RQYQ14P |
RQYQ16P |
|
Outdoor unit module 2 |
|
RQYQ10P |
RQYQ12P |
RQYQ12P |
RQYQ16P |
RQYQ16P |
RQYQ10P |
RQYQ16P |
RQYQ16P |
RQYQ10P |
|
RQYQ12P |
RQYQ16P |
RQYQ16P |
RQYQ12P |
RQYQ16P |
RQYQ12P |
RQYQ16P |
|
|
|
|
|
Outdoor unit module 3 |
|
|
|
|
|
|
RQYQ16P |
|
RQYQ16P |
RQYQ14P |
|
RQYQ16P |
RQYQ16P |
RQYQ16P |
|
|
RQYQ16P |
RQYQ16P |
|
|
|
|
Recommended combination |
4 x FXSQ32A2VEB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling capacity |
Prated,c |
kW |
14.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating capacity |
Prated,h |
kW |
16.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Space cooling |
A Condition (35°C - 27/19) |
EERd |
|
2.54 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdc |
kW |
14.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B Condition (30°C - 27/19) |
EERd |
|
4.40 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdc |
kW |
10.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C Condition (25°C - 27/19) |
EERd |
|
7.31 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdc |
kW |
6.63 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D Condition (20°C - 27/19) |
EERd |
|
9.29 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdc |
kW |
5.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Space heating (Average climate) |
TBivalent |
COPd (declared COP) |
|
1.92 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
8.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TOL |
COPd (declared COP) |
|
1.92 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
8.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A Condition (-7°C) |
COPd (declared COP) |
|
2.20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
7.52 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B Condition (2°C) |
COPd (declared COP) |
|
3.42 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
4.58 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C Condition (7°C) |
COPd (declared COP) |
|
4.84 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
3.29 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D Condition (12°C) |
COPd (declared COP) |
|
6.43 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pdh (declared heating cap) |
kW |
4.18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacity range |
HP |
5 |
18 |
22 |
24 |
30 |
26 |
36 |
28 |
42 |
34 |
8 |
38 |
46 |
48 |
20 |
32 |
40 |
44 |
10 |
12 |
14 |
16 |
Maximum number of connectable indoor units |
10 |
39 |
47 |
52 |
64 |
56 |
64 |
60 |
64 |
64 |
17 |
64 |
64 |
64 |
43 |
64 |
64 |
64 |
21 |
26 |
30 |
34 |
Indoor index connection |
Min. |
|
62.5 |
225 |
275 |
300 |
375 |
325 |
450 |
350 |
525 |
425 |
100 |
475 |
575 |
600 |
250 |
400 |
500 |
550 |
125 |
150 |
175 |
200 |
|
Nom. |
|
125 |
450 |
550 |
600 |
750 |
650 |
900 |
700 |
1,050 |
850 |
200 |
950 |
1,150 |
1,200 |
500 |
800 |
1,000 |
1,100 |
250 |
300 |
350 |
400 |
|
Max. |
|
162.5 |
585 |
715 |
780 |
975 |
845 |
1,170 |
910 |
1,365 |
1,105 |
260 |
1,235 |
1,495 |
1,560 |
650 |
1,040 |
1,300 |
1,430 |
325 |
390 |
455 |
520 |
Dimensions |
Unit |
Height |
mm |
1,680 |
|
|
|
|
|
|
|
|
|
1,680 |
|
|
|
|
|
|
|
1,680 |
1,680 |
1,680 |
1,680 |
|
|
Width |
mm |
635 |
|
|
|
|
|
|
|
|
|
930 |
|
|
|
|
|
|
|
930 |
930 |
1,240 |
1,240 |
|
|
Depth |
mm |
765 |
|
|
|
|
|
|
|
|
|
765 |
|
|
|
|
|
|
|
765 |
765 |
765 |
765 |
Weight |
Unit |
kg |
175 |
|
|
|
|
|
|
|
|
|
230 |
|
|
|
|
|
|
|
284 |
284 |
381 |
381 |
Fan |
External static pressure |
Max. |
Pa |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
Compressor |
Type |
|
Hermetically sealed scroll compressor |
|
|
|
|
|
|
|
|
|
Hermetically sealed scroll compressor |
|
|
|
|
|
|
|
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Operation range |
Cooling |
Min. |
°CDB |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
-5 |
|
|
Max. |
°CDB |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
|
Heating |
Min. |
°CWB |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
|
|
Max. |
°CWB |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
Sound power level |
Cooling |
Nom. |
dBA |
79 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound pressure level |
Cooling |
Nom. |
dBA |
|
61 |
63 |
63 |
63 |
63 |
64 |
63 |
65 |
64 |
57.0 |
65 |
65 |
65 |
62 |
63 |
65 |
65 |
58.0 |
60.0 |
60.0 |
60.0 |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
|
Charge |
kg |
11.1 |
|
|
|
|
|
|
|
|
|
10.8 |
|
|
|
|
|
|
|
11.7 |
11.7 |
11.7 |
11.7 |
|
Charge |
TCO2Eq |
23.2 |
|
|
|
|
|
|
|
|
|
22.5 |
|
|
|
|
|
|
|
24.4 |
24.4 |
24.4 |
24.4 |
Piping connections |
Liquid |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
9.52 |
15.9 |
15.9 |
15.9 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
9.52 |
19.1 |
19.1 |
19.1 |
15.9 |
19.1 |
19.1 |
19.1 |
9.52 |
12.7 |
12.7 |
12.7 |
|
Gas |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
15.9 |
28.6 |
28.6 |
34.9 |
34.9 |
34.9 |
41.3 |
34.9 |
41.3 |
34.9 |
19.1 |
41.3 |
41.3 |
41.3 |
28.6 |
34.9 |
41.3 |
41.3 |
22.2 |
28.6 |
28.6 |
28.6 |
|
Total piping length |
System |
Actual |
m |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
|
Level difference |
OU - IU |
Outdoor unit in highest position |
m |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
|
|
Indoor unit in highest position |
m |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
40 |
|
|
IU - IU |
Max. |
m |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
Power supply |
Name |
|
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
|
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
Notes |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
|
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - TOCA means the total value of each OC set. |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
|
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - MSC means the maximum current during start up of the compressor |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
(4) - TOCA means the total value of each OC set. |
|
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
(5) - MSC means the maximum current during start up of the compressor |
|
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Maximum allowable voltage range variation between phases is 2%. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Select wire size based on the value of MCA or TOCA. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
(7) - Maximum allowable voltage range variation between phases is 2%. |
|
(8) - Select wire size based on the larger value of MCA or TOCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
(8) - Select wire size based on the value of MCA |
|
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
|
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Contains fluorinated greenhouse gases |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Contains fluorinated greenhouse gases |
(10) - Contains fluorinated greenhouse gases |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Contains fluorinated greenhouse gases |
(10) - Contains fluorinated greenhouse gases |
(10) - Contains fluorinated greenhouse gases |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Contains fluorinated greenhouse gases |
(10) - Contains fluorinated greenhouse gases |
(10) - Contains fluorinated greenhouse gases |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
(10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. |
|
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
|
(11) - Contains fluorinated greenhouse gases |
|
|
(11) - Contains fluorinated greenhouse gases |
|
|
|
(11) - Contains fluorinated greenhouse gases |
|
|
|
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |
(11) - Contains fluorinated greenhouse gases |