EWYD4004ZXRA2 EWYD4504ZXRA2 EWYD5004ZXRA2 EWYD5504ZXRA2 EWYD6004ZXRA2 EWYD6504ZXRA2 EWYD7004ZXRA2 EWYD8004ZXRA2
Air to Water - Cooling only mode Air to Water - Cooling only mode-=-Cooling capacity Air to Water - Cooling only mode-=-Cooling capacity-=-Nom. Air to Water - Cooling only mode-=-Cooling capacity-=-Nom.-=-Gross-=-kW kW 358 401 453 497 549 598 620 691
      Air to Water - Cooling only mode-=-Cooling capacity-=-Nom.-=-Net-=-kW kW 358 400 452 496 548 597 619 690
  Air to Water - Cooling only mode-=-EER Air to Water - Cooling only mode-=-EER-=-Gross   3.07 3.08 3.15 3.09 3.13 3.10 3.22 3.10
    Air to Water - Cooling only mode-=-EER-=-Net   3.05 3.06 3.12 3.06 3.11 3.07 3.19 3.08
Air to Water - Heating only mode Air to Water - Heating only mode-=-Heating capacity Air to Water - Heating only mode-=-Heating capacity-=-Nom. Air to Water - Heating only mode-=-Heating capacity-=-Nom.-=-Gross-=-kW kW 358 398 451 492 549 599 620 689
      Air to Water - Heating only mode-=-Heating capacity-=-Nom.-=-Net-=-kW kW 358 399 452 493 551 601 621 691
  Air to Water - Heating only mode-=-COP Air to Water - Heating only mode-=-COP-=-Gross   3.49 3.66 3.66 3.65 3.61 3.58 3.70 3.74
    Air to Water - Heating only mode-=-COP-=-Net   3.48 3.65 3.65 3.63 3.59 3.55 3.67 3.71
Water to Water - Cooling + Heating mode Water to Water - Cooling + Heating mode-=-Cooling capacity Water to Water - Cooling + Heating mode-=-Cooling capacity-=-Gross-=-kW kW 280 313 356 389 436 474 488 545
    Water to Water - Cooling + Heating mode-=-Cooling capacity-=-Net-=-kW kW 280 313 355 388 435 473 486 544
  Water to Water - Cooling + Heating mode-=-Heating capacity Water to Water - Cooling + Heating mode-=-Heating capacity-=-Gross-=-kW kW 359 399 452 493 549 599 623 692
    Water to Water - Cooling + Heating mode-=-Heating capacity-=-Net-=-kW kW 360 400 453 494 551 601 624 694
  Water to Water - Cooling + Heating mode-=-TER Water to Water - Cooling + Heating mode-=-TER-=-Gross-=-kW kW 8.10 8.28 8.34 8.46 8.69 8.58 8.22 8.41
    Water to Water - Cooling + Heating mode-=-TER-=-Net-=-kW kW 7.99 8.17 8.20 8.29 8.51 8.38 8.05 8.23
Dimensiones Unidad Altura mm 2,455 2,455 2,455 2,455 2,455 2,455 2,455 2,455
    Anchura mm 2,240 2,240 2,240 2,240 2,240 2,240 2,240 2,240
    Profundidad mm 5,775 5,775 6,675 6,675 7,575 8,475 8,475 8,475
Peso Unidad kg 7,100 7,210 7,980 7,980 8,750 9,520 9,720 9,720
  Peso operativo kg 7,398 7,508 8,482 8,460 9,328 10,098 10,307 10,298
Cold Water heat exchanger Cold Water heat exchanger-=-Water volume-=-l l 149 149 262 240 298 298 307 280
  Cold Water heat exchanger-=-Water flow rate Cold Water heat exchanger-=-Water flow rate-=-Nom.-=-l/s l/s 17.1 19.1 21.6 23.7 26.2 28.5 29.6 33.0
  Cold Water heat exchanger-=-Water pressure drop Cold Water heat exchanger-=-Water pressure drop-=-Nom.-=-kPa kPa 30.5 37.4 31.5 36.7 36.9 26.3 31.6 27
Hot Water heat exchanger Hot Water heat exchanger-=-Water volume-=-l l 149 149 240 240 280 280 298 298
  Hot Water heat exchanger-=-Water flow rate Hot Water heat exchanger-=-Water flow rate-=-Nom.-=-l/s l/s 17.3 19.3 21.8 23.8 26.6 29.0 30.0 33.3
  Hot Water heat exchanger-=-Water pressure drop Hot Water heat exchanger-=-Water pressure drop-=-Nom.-=-kPa kPa 31.2 37.5 28.2 32.9 32 22.9 26.3 23.3
Ventilador Cantidad   10 10 12 12 14 16 16 16
  Caudal de aire Nom. l/s 19,444 19,444 23,333 23,333 27,222 31,111 31,111 31,111
Compresor Compressor-=-Type   Compresor monotornillo Compresor monotornillo Compresor monotornillo Compresor monotornillo Compresor monotornillo Compresor monotornillo Compresor monotornillo Compresor monotornillo
  Cantidad_   2 2 2 2 2 2 2 2
Nivel de potencia sonora Refrigeración Nom. dBA 87 86 87 87 88 88 90 90
  Calefacción Nom. dBA 88 88 89 89 89 90 91 92
Nivel de presión sonora Refrigeración Nom. dBA 66 66 66 66 66 66 68 69
  Calefacción Nom. dBA 68 67 68 68 68 68 69 70
Límites de funcionamiento Lado del aire Refrigeración Mín. °CBS -10 -10 -10 -10 -10 -10 -10 -10
      Máx. °CBS 46 46 46 46 46 46 46 46
    Calefacción Mín. °CBS -10 -10 -10 -10 -10 -10 -10 -10
      Máx. °CBS 45 45 45 45 45 45 45 45
  Lado del agua Refrigeración Mín. °CBS -8 -8 -8 -8 -8 -8 -8 -8
      Máx. °CBS 20 20 20 20 20 20 20 20
    Calefacción Mín. °CBS 30 30 30 30 30 30 30 30
      Máx. °CBS 55 55 55 55 55 55 55 55
Refrigerante Type   R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
  Carga kg 170 175 190 210 235 255 265 285
  Circuitos Cantidad   2 2 2 2 2 2 2 2
Conexiones de tubería Piping connections-=-Cold / Hot heat exchanger water inlet / outlet (OD)-=-mm mm 139.7 139.7 168.3 168.3 168.3 168.3 168.3 168.3
Alimentación eléctrica Fase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frecuencia Hz 50 50 50 50 50 50 50 50
  Tensión V 400 400 400 400 400 400 400 400
Unidad Corriente de func. Refrigeración Nom. A 212 232 253 278 300 327 326 372
    Máx. A 250 257 286 305 335 370 393 425
  Corriente de la unidad máx. para el tamaño de los cables A 269 277 310 330 364 403 428 463
Ventiladores Corriente nominal de funcionamiento A 5 5 6 6 7 8 8 8
Compresor Fase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Tensión V 400 400 400 400 400 400 400 400
  Límites de tensión Mín. % -10 -10 -10 -10 -10 -10 -10 -10
    Máx. % 10 10 10 10 10 10 10 10
  Corriente máxima de funcionamiento A 245 252 280 299 328 362 385 417
  Método de arranque_   Con control Inverter Con control Inverter Con control Inverter Con control Inverter Con control Inverter Con control Inverter Con control Inverter Con control Inverter
Notas (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C. (1) - Operation in Air to water “Cooling only” mode rated at 35°C ambient temperature, 50% R.H.; Entering water temperature 12°C, Outlet water temperature 7°C.
  (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C. (2) - Operation in Air to water “Heating only” mode rated at 7°C ambient temperature, 85% R.H; Entering water temperature 40°C, Outlet water temperature 45°C.
  (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only". (3) - Operation in Water to water “Cooling + Heating” mode rated with water flowing on cold and hot heat exchangers determined respectively at conditions for "Cooling only" and "Heating only".
  (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C. (4) - Chilled water outlet temperature 7°C, Hot water outlet temperature 45°C.
  (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating. (5) - Sound power level are referred to condition (1) for Cooling and (2) for Heating.
  (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1 (6) - El nivel de potencia sonora (con evaporador 12/7 °C, ambiente 35 °C y funcionamiento a plena carga) se mide conforme a ISO 9614 y Eurovent 8/1
  (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level. (7) - The certification refers only to the overall sound power level.
  (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante (8) - El nivel de presión sonora se calcula a partir del nivel de potencia sonora y solo sirve de referencia, no es vinculante
  (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios. (9) - Todos los datos hacen referencia a la unidad estándar sin accesorios.
  (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad. (10) - Todos los datos están sujetos a cambios sin previo aviso. Consulte los datos de la placa de identificación de la unidad.