Tabla de especificaciones técnicas GSIEKA

GSIEKA10009 GSIEKA15018 GSIEKA25030 GSIEKA20024 GSIEKA35530
Capacidad kW 0.9 1.8 3.0 2.4 3.0
Diámetro del conducto mm 100 150 255 200 355
Connectable unit VAM150FCVE(9) VAM250FCVE(9), VAM350FCVE VAM650-800-1000J7VE, VAM1500-2000J7VEB, VAM800-1000FCVE VAM350-500J7VEB, VAM500-650FCVE VAM1500-2000J7VEB, VAM1500-2000FCVE
Corriente de salida (máxima) 4,1A 8,2A 13,6A 10,9A 13,6A
Temperature sensor 10 kΩ at 25°C 10 kΩ at 25°C 10 kΩ at 25°C 10 kΩ at 25°C 10 kΩ at 25°C
Temperature control range -10…50°C -10…50°C -10…50°C -10…50°C -10…50°C
LED indicators LED 1 flashing every 5 sec - Heater is starting up, LED 1 flashing every sec - Ari flow detected, heating allowed, LED 1 OFF - No power supply or no flow, LED 1 ON - Problem with duct temperature sensor, setpoint potentiometer or PTC airflow sensor, LED 2 OFF - Heater is not operating, LED 2 ON - Heater is operating LED 1 flashing every 5 sec - Heater is starting up, LED 1 flashing every sec - Ari flow detected, heating allowed, LED 1 OFF - No power supply or no flow, LED 1 ON - Problem with duct temperature sensor, setpoint potentiometer or PTC airflow sensor, LED 2 OFF - Heater is not operating, LED 2 ON - Heater is operating LED 1 flashing every 5 sec - Heater is starting up, LED 1 flashing every sec - Ari flow detected, heating allowed, LED 1 OFF - No power supply or no flow, LED 1 ON - Problem with duct temperature sensor, setpoint potentiometer or PTC airflow sensor, LED 2 OFF - Heater is not operating, LED 2 ON - Heater is operating LED 1 flashing every 5 sec - Heater is starting up, LED 1 flashing every sec - Ari flow detected, heating allowed, LED 1 OFF - No power supply or no flow, LED 1 ON - Problem with duct temperature sensor, setpoint potentiometer or PTC airflow sensor, LED 2 OFF - Heater is not operating, LED 2 ON - Heater is operating LED 1 flashing every 5 sec - Heater is starting up, LED 1 flashing every sec - Ari flow detected, heating allowed, LED 1 OFF - No power supply or no flow, LED 1 ON - Problem with duct temperature sensor, setpoint potentiometer or PTC airflow sensor, LED 2 OFF - Heater is not operating, LED 2 ON - Heater is operating
Orificios de montaje 100mm 150mm 250mm 200mm 355mm
Maximum ambient adjacent to terminal box 50°C 50°C 50°C 50°C 50°C
Run relay 230VAC/20A 230VAC/20A 230VAC/20A 230VAC/20A 230VAC/20A
Entrada de punto de ajuste BMS 0-10 V de CC 0-10 V de CC 0-10 V de CC 0-10 V de CC 0-10 V de CC
Alimentación eléctrica Frecuencia Hz 50/60 50/60 50/60 50/60 50/60
  Tensión V 230 230 230 230 230
Fusible de control 250V/315mA 250V/315mA 250V/315mA 250V/315mA 250V/315mA