Tabla de especificaciones técnicas EWFH-TZPSD

EWFH225TZPSD1 EWFH265TZPSD1 EWFH295TZPSD1 EWFH340TZPSD1 EWFH395TZPSD1 EWFH420TZPSD1 EWFH490TZPSD1 EWFH500TZPSD2 EWFH540TZPSD2 EWFH545TZPSD1 EWFH615TZPSD2 EWFH645TZPSD2 EWFH700TZPSD2 EWFH770TZPSD2 EWFH845TZPSD2 EWFH900TZPSD2 EWFH960TZPSD2 EWFHC10TZPSD2 EWFHH10TZPSD2 EWFHH11TZPSD2 EWFHC12TZPSD2
Capacidad de refrigeración Nom. kW 314.39 377.84 413.94 481.12 545.38 672.02 716.4 762.26 868.15 709.3 901.97 965.07 1,058.6 1,166.75 1,227.87 1,313.47 1,373.69 1,471.78 1,527.41 1,605.75 588.19
Control de capacidad Método   Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua Regulación continua
  Capacidad mínima % 21.5 19 16.5 27.5 23 21.5 19 10 10 30 15 13.5 12.5 11.5 10.5 10 10 10 10 13.5 13.5
Consumo Refrigeración Nom. kW 66.38 77.51 89.54 93.35 114.38 148.22 142.4 153.37 175.31 142.95 186.01 209.12 227.02 248.93 274.14 293.71 318.72 343.47 314.15 328.91 123.39
EER 4.736 4.875 4.623 5.154 4.768 4.534 5.031 4.97 4.952 4.962 4.849 4.615 4.663 4.687 4.479 4.472 4.31 4.285 4.862 4.882 4.767
IPLV 6.738 6.736 6.579 7.506 7.214 7.271 7.135 6.819 6.956 6.73 7.347 7.226 7.016 7.052 7.143 6.966 6.615 6.787 6.825 6.965 7.041
SEER 6.008 6.095 6.081 6.58 6.397 6.579 6.481 6.199 6.24 5.753 6.646 6.55 5.945 6.46 6.506 6.388 5.929 6.3 5.568 6.031 6.095
Dimensiones Unidad Profundidad mm 3640 4720 4720 5800 5800 6880 6880 6880 7960 6880 7960 7960 7960 9040 10120 10120 11200 11200 12280 12280 13360
    Altura mm 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553
    Anchura mm 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238
Peso Peso operativo kg 3628 4254 4259 5,223.1 5,233.1 5,813.1 5,939.3 6391 6971 6,618.3 7900 7905 7910 8765 9329 9339 11225 11235 11797 12476 13061
  Unidad kg 3307 3846 3846 4720 4720 5229 5315 5336 5846 5984 6358 6358 6358 6957 7519 7519 8341 8341 8892 9561 10070
Carcasa Color   Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil Blanco marfil
  Material   Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada Lámina de acero galvanizado pintada
Evaporador del intercambiador de calor de agua Tipo   Placa cobresoldada Placa cobresoldada Placa cobresoldada Placa cobresoldada Placa cobresoldada Placa cobresoldada Placa cobresoldada Cuerpo y tubo Cuerpo y tubo Placa cobresoldada Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo Cuerpo y tubo
  Volumen de agua l 40 48 48 58.1 58.1 58.1 76.3 289 289 76.3 492 492 492 583 546 546 1043 1043 1011 1011 1011
Intercambiador de calor de agua: evaporador Caída de presión del agua Refrigeración Nom. kPa 7.09 8.03 9.6 11.36 14.61 12.86 14.59 17.06 22.12 14.92 23.78 26.91 25.34 35.85 39.55 23.02 24.93 19.69 20.93 22.71 16.96
Intercambiador de calor de aire Tipo   Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal
Ventilador Cantidad   6 8 8 10 10 12 12 12 14 12 14 14 14 16 18 18 20 20 22 22 24
  Tipo   Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo Helicoidal directo
  Caudal de aire Refrigeración Nom. l/s 33765 45020 45020 56275 56275 67530 67530 67530 78785 67530 78785 78785 78785 90040 101295 101295 112550 112550 123805 123805 135060
Motor del ventilador Transmisión   Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas Sin escobillas
Compresor Cantidad   1 1 1 1 1 1 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2
  Tipo   Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo Compresor de tornillo
Límites de funcionamiento Lado del aire Refrigeración Mín. °CBS -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
      Máx. °CBS 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46
  Lado del agua Evaporador Mín. °CBS 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
      Máx. °CBS 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
Nivel de potencia sonora Refrigeración Nom. dBA 97.48 98.1 102.57 95.74 98.68 100.06 104.55 100.6 100.91 98.99 96.61 97.51 99.32 100.95 102.3 104.16 106.51 106.87 105.5 102.36 102.82
Nivel de presión sonora Refrigeración Nom. dBA 77.74 77.83 82.3 75 77.94 78.89 83.39 79.43 79.35 77.82 75.06 75.95 77.76 79.04 80.05 81.92 83.96 84.32 82.67 79.52 79.71
Refrigerante Tipo   R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze)
  GWP   7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7
  Carga kg 30 35 40 45 55 60 65 70 75 75 85 90 95 105 115 125 130 140 150 160 170
  Circuitos Cantidad   1 1 1 1 1 1 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2
Conexiones de tubería Entrada/salida de agua del evaporador (D.E.)   88.9 88.9 88.9 139.7 139.7 139.7 139.7 168.3 168.3 139.7 219.1 219.1 219.1 219.1 219.1 219.1 273 273 273 273 273
Alimentación eléctrica Fase   3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
  Frecuencia Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Tensión V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
  Límites de tensión Mín. % -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    Máx. % 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Unidad Corriente de arranque Máx. A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
  Corriente de func. Máx. A 183 214 235 258 301 330 367 375 406 425 432 458 505 558 609 647 694 731 779 875 923
  Corriente de la unidad máx. para el tamaño de los cables A 201 235 258 283 331 363 404 412 444 467 476 503 556 614 670 712 764 804 857 962 1015
Notas (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol
  (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187
  (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1
  (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow.
  (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition
  (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C
  (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%.